44
FACING AND FINISHING
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
#CLW-ST R.1 February 2021
17”
(432mm)
76”
(1930mm)
19
¾
”
(502mm)
29
½
”
(750mm)
9
¾
”
(248mm)
3”
(76mm)
6” (152mm)
9” (229mm)
12” (305mm)
6” (152mm)
9” (229mm)
12” (305mm)
Each square represents
1” (25mm) of projection
Combustible wall finish
may be installed over required
non-combustible material
and butt up to the finishing
edge around the opening
Top finishing edge
Bottom
finishing edge
Non-combustible material
(both sides of fireplace)
Fireplace Enclosure Floor
Non-combustible zone
No surround
Figure 4.11, Vented Cavity & KZK Facing and Finishing Clearances - No Surround
(single opening vented cavity installation shown)
VENTED CAVITY AND KZK INSTALLATIONS ONLY
Nominal 2”x 4” framing used