Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
FRAMING
25
60”
(1524mm)
MIN
Ceiling
Air Discharge Opening
Figure 3.17, Clearance from Air Discharge Opening to Sprinkler Head
3.9.2 Cl
earance to Sprinkler
•
In a situation where a sprinkler head is installed within the
proximity of a vented cavity air discharge opening, Figure 3.17
MUST be followed.
•
The distance between a sprinkler head and discharge opening
cannot be less than 60” (1524mm) in length at every point from
the origin of the discharge opening. You must also verify the
sprinkler head sensor is set to the proper heat setting so it does
not activate when the room heats up from the fireplace being
operated normally.
•
Please follow local building codes to determine what
temperature setting is relevant for your installation.
ALL VENTED CAVITY INSTALLATIONS ONLY