Page 16

EXTERNALLY ADJUSTABLE VENTURI.  FIGURES 12A - 12C.

An externally adjustable venturi has been incorporated into the millivolt board assembly for this fireplace.  Follow the instructions
below for proper operation and settings.

CAUTION: 

THE SURFACES OF THIS FIREPLACE ARE HOT WHILE THE BURNER IS IN OPERATION. ALLOW THE FIREPLACE TO

COOL PRIOR TO ADJUSTING THE VENTURI OR USE EXTREME CAUTION AND WEAR THE APPROPRIATE

PROTECTION TO AVOID SERIOUS BURNS.

Referring to the millivolt board above, locate the adjustable venturi lever attached to
the bottom of the millivolt board.

1. The venturi has been factory set for a typical minimum venting configuration

using Natural Gas.

Natural Gas: Lever is positioned in the left notched out section of the bracket

as shown in Figure 12A.  This is approximately 1/4" opened.

LP Gas: Lever is positioned in the right notched out section of the

bracket as shown in Figure 12B.  This is approximately 5/8" opened.   

      

                    

       

Figure 12A

The lever may be adjusted in small increments by pulling the lever down slightly
and sliding it in either direction, placing the slots in the lever(under the millivolt
board) into the smaller notches on either side of the factory-set positions.

ADJUSTMENTS:

Placing the lever to the right will close the venturi air collar allowing less air 
to be mixed with the gas in the burner tube.

Placing the lever to the left opens the venturi collar allowing more air to be

     

   

mixed with the gas in the burner tube.

                 

Figure 12B

    

    

NOTE: 

Each fireplace installation is different - i.e.: Venting configuration, chimney system used, etc.   Adjust the venturi
opening as necessary to achieve proper burn and appearance.

CAUTION: Do not close the shutter too far!  This will cause the fireplace to burn ‘dirty’ which will result in soot

accumulation inside the glass, the firebox and possibly the logs.

     Figure 12C

VENTURI COLLAR SHOWN IN 

     THE ‘OPENED’ POSITION

LEVER

VENTURI COLLAR

Содержание 961 DV

Страница 1: ...ht any appliance Do not touch electrical switches do not use the phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas suppliers instructions If you cannot r...

Страница 2: ...0 Fan Installation 11 12 Minimum Maximum Gas Supply Pressure Run the Gas Line 13 14 Millivolt Board Removal Installation 14 16 Log Installation 17 Wall Switch Thermostat Remote Control Installation 18...

Страница 3: ...m and battery back up may be installed on the next adjacent floor level In the event that the requirements of this subdivision can not be met at the time of completion of installation the owner shall...

Страница 4: ...e manufacturer of Product Approved side wall horizontally vented gas equipment does not provide the parts for venting the flue gases but identifies special venting systems the following requirements s...

Страница 5: ...en Installed Within The Commonwealth of Massachusetts IMPORTANT Installation of a CO detector is required in the fireplace room WARNING DO NOT REPLACE THIS BURNER WITH ANY OTHER SIZED BURNER REPLACEME...

Страница 6: ...ow instructions included with the Simpson Dura Vent DV GS for position of chimney The 923 C adaptor must be used 6 All clearances to combustible requirements must be maintained Follow clearance requir...

Страница 7: ...not left the fireplace may make a loud banging noise when it heats up or cools down 10 Cut an opening for the wall thimble 9 x 9 The top of this opening must be a minimum of 47 1 4 above the height o...

Страница 8: ...ng used a lintel part 788B must be used over the top of the fireplace to support the added weight NOTE Provide for a minimum of 6 152 mm of clearance in front of the lower grill This will provide adeq...

Страница 9: ...TING REQUIREMENTS IMPORTANT This fireplace is approved for use only with one of the following direct vent systems HORIZONTAL TERMINATIONS 700 SERIES DIRECT VENT TERMINATION KITS Used for horizontal te...

Страница 10: ...izontal runs up to 2 ft must have a minimum vertical rise of 17 EXAMPLE 2 If the horizontal run is 8 ft the vertical rise required is 28 EXAMPLE 3 If the horizontal run is 21 ft the vertical rise requ...

Страница 11: ...ted soffit 12 E S Outside inside corner 12 F S Meter Regulator Not to be installed above within 3 ft horizontally from the center line of the regulator S Service regulator vent outlet 3 ft radius S No...

Страница 12: ...install the restrictor refer to Figures 7A 7B and bend the tabs up far enough approximately 80 degrees so that when positioned into the exhaust pipe will create tension to hold itself in place Do not...

Страница 13: ...7 pipes onto the previous extension kit Referring to Figure 9 7 Apply a liberal bead of exterior sealant around the outer edge of the termination kit box A and from the outside place the exterior wall...

Страница 14: ...m and is available from your dealer Follow the installation instructions included with the 923 C adaptor AND chimney system This chimney system may be purchased from your local dealer Maximum vertical...

Страница 15: ...t fan assemblies with magnetic limit switch already mounted 2 Components package 4 nuts installation instructions NOTE To wall mount the speed control you will need to purchase a speed control assembl...

Страница 16: ...9 Re install the electrical access panel and secure 10 Place the thermostatic control switch with magnet on the bottom of the firebox 11 Plug the fan cord E into the receptacle in the electrical box...

Страница 17: ...d flexible gas line will connect CAUTION The manual shut off valve or flexible gas tubing must not extend outside of the fireplace cavity See the WARNING label affixed to the flexible tubing for addit...

Страница 18: ...gas valve The right pressure tap is the manifold pressure and the left pressure tap is the incoming pressure FOLLOW INSTRUCTIONS ON PAGE 24 OF THIS MANUAL G MILLIVOLT BOARD BURNER ASSEMBLY REMOVAL IN...

Страница 19: ...Re install the pilot shield Figure 11D 4 Re install the burner cover aligning the mounting holes in the burner brackets to the corresponding mounting studs on the bottom of the millivolt board Figure...

Страница 20: ...t notched out section of the bracket as shown in Figure 12B This is approximately 5 8 opened Figure 12A The lever may be adjusted in small increments by pulling the lever down slightly and sliding it...

Страница 21: ...notches to the burner cover Figure 13B 3 Place the center logs BW6 BW7 over the base BW7 logs aligning the holes and or notches in the logs BW6 to the base logs Figure 13B BW4 BW5 Figure 13B 4 Brush r...

Страница 22: ...iate connector to each wall switch thermostat wire and connect to the top and bottom terminals on the gas valve REMOTE CONTROL USERS Follow instructions included with the remote control IMPORTANT The...

Страница 23: ...ound Attach the appropriate set for your application Align the 3 holes on each side of the fireplace to the slots on each trim piece and secure with the screws provided 3 ea Side Figure 15 3 COMPLETE...

Страница 24: ...CLOSED POSITION IN PARTIAL OPENED POSITION 5 START UP THIS STEP SHOULD ONLY BE DONE BY A QUALIFIED INSTALLER OR SERVICE TECHNICIAN A Make sure the burner tube is properly seated over the burner orific...

Страница 25: ...wer hole and release The grill will set down into place Lower grills See Figure 18 A The lower grills attach to the hinges A located at the bottom of the fireplace B Remove the 1 4 nuts B from the low...

Страница 26: ...t the thermostat if used to the lowest setting 3 Turn off all electric power to the appliance 4 Push in control knob A slightly and turn clockwise to OFF Gas Valve NOTE Knob cannot be turned from PILO...

Страница 27: ...19 NOTE A PAINT SMELL WILL OCCUR DURING THE FIRST FEW HOURS OF BURNING IT IS RECOMMENDED TO LEAVE THE FAN OFF DURING THIS PERIOD AS THIS WILL SPEED UP THE PAINT CURING PROCESS INITIAL BURN PERIOD DUE...

Страница 28: ...d ON NOTE If manifold pressure reading is within the normal range an incoming pressure check is not necessary A too high or too low pressure reading warrants an inlet incoming gas pressure check TO CH...

Страница 29: ...x near the top and remove the baffle 6 Examine proper sealing of the vent system 7 Re install the baffle and nuts Tighten nuts only enough to secure baffle Baffle must be able to float as the fireplac...

Страница 30: ...E SOLUTION 1 No spark when piezo The nut which holds the piezo Tighten nut button is depressed in place is loose Wire on back of piezo button Put wire back into place is loose or off Wire from piezo t...

Страница 31: ...ay due to pinching of wires need loosening to remove pinched wire Generator is not producing enough Replace generator millivolts to operate burner Wall switch remote control or Connect properly or dis...