E) RUN THE GAS LINE.
CAUTION: Installation of the gas line must only be done by a qualified person in accordance with local building
codes.
GAS CONVERSIONS:
This fireplace is manufactured for use with Natural Gas. An LP Gas conversion kit is included with this fireplace.
Follow instructions included with this conversion kit.
Natural Gas Conversion Kit #OCK-S31A - used to convert an LP millivolt board to Natural Gas.
LP Gas Conversion Kit #OCK-S50A - used to convert a Natural Gas millivolt board to LP Gas.
The conversion shall be carried out in accordance with the requirements of the provincial authorities having jurisdiction
and in accordance with the requirements of ANSI Z223.1 installation code.
NOTE: This fireplace is equipped with a flexible gas connector and manual shut off valve.
NOTE: The gas line should be run to the point of connection where the shut-off valve and flexible gas line will
connect.
CAUTION: The manual shut-off valve or flexible gas tubing must not extend outside of the fireplace cavity. See the
WARNING label affixed to the flexible tubing for additional installation instructions and warnings.
NATURAL GAS:
The minimum inlet gas supply pressure: 7.0 inches W.C. (recommended)
The maximum inlet gas supply pressure: 10.5 inches W.C.
Manifold pressure: 3.5 inches W.C.
Manifold pressure (lo setting): 1.7 inches W.C.
Orifice size (0-2000 ft.): 31 Input: 38,000 BTU’s
LP GAS:
The minimum inlet gas supply pressure: 11.0 inches W.C. (recommended)
The maximum inlet gas supply pressure: 13.0 inches W.C.
Manifold Pressure: 10.0 inches W.C.
Manifold Pressure (lo setting): 6.3 inches W.C.
Orifice size (0-2000 ft.): 50
Input: 38,000 BTU’s
NOTE:
For high altitude installations consult the local gas distributor or the authority
having jurisdiction for proper rating methods.
1. Run the gas line. An accessible shut off valve must be installed up stream from the regulator.
NOTE: Do not run the incoming gas line in a manner that would obstruct the operation of the fan.