COMMONWEALTH OF MASSACHUSETTS REQUIREMENTS                        

NOTE: The following requirements reference various Massachusetts and national codes not contained in this manual. 

For all sidewall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes,  
including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than (7) feet above finished grade in the  
area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:  

INSTALLATION OF CARBON MONOXIDE DETECTORS 

At time of installation of side wall horizontally vented gas fueled equipment, the installing plumber or gas-fitter shall observe that a hard wired carbon mon-
oxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber 
or gas-fitter shall observe that a battery operated or hard wired carbon monoxide detector is installed on each additional level of the dwelling, building or 
structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified 
licensed professionals for the installation of hard wired carbon monoxide detectors.  
 
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or attic, the hard wired carbon monoxide detector with 
alarm and battery back-up may be installed on the next adjacent floor level. 
 
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days 
to comply  with the above requirements; provided, however, that during said thirty (30) day period, a battery  operated carbon  monoxide detector with an 
alarm shall be installed. 

APPROVED CARBON MONOXIDE DETECTORS 

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS 
certified. 

SIGNAGE 

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum of eight (8) feet above grade directly in line 
with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print no less the one-half inch 
(1/2) in size, 

 “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

  

INSPECTION 

The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the  
inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08 (2) (a) 1 through 4. 

EXEMPTIONS 

The following equipment is exempt from 248 CMR 5.08 (2) (a) 1 through 4:The equipment listed in Chapter 10 entitled “Equipmen

t Not Required To Be 

Vented” in the most current edition of NFPA 54 as adopted by the Board; and Product Approved side wall horizontally vented ga

s fueled equipment installed 

in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes. 

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED 

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components 
with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include: 
  
 

Detailed instructions for the installation of the venting system design or the venting system components; and 

 
 

A complete parts list for the venting system design or venting system. 

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM  NOT PROVIDED 

When the manufacturer of Product Approved side wall horizontally vented gas equipment does not provide the parts for venting the flue gases, but identifies 

“special venting systems”, the following requirements shall be satisfied by the manufacturer:

 

 
 

The referenced “special venting systems” instructions shall be included with the appliance or equipment installation instruct

ions and;   

 
 

The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a pa

rts list and detailed  

 

installation instructions. 

 
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for 
venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation. 
 

Содержание 911-XXL

Страница 1: ...the vicinity of this or any other appliance IF YOU SMELL GAS Do not light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call gas supplier from a ne...

Страница 2: ...on and reliability but customer safety as well We offer our continual support and guidance to help you achieve the maximum benefit and enjoyment from your Kozy Heat gas fireplace Jim Hussong Dudley Hu...

Страница 3: ...ormation 1 TABLE OF CONTENTS Table of Contents 2 SAFETY INFORMATION Safety Information 3 FEATURES Features 4 COMMONWEALTH OF MASSACHUSETTS INFORMATION Commonwealth of Massachusetts Information 5 SPECI...

Страница 4: ...d other at risk individuals out of the room and away from hot surfaces Clothing or other flammable material should not be place on or near the appliance Adequate accessibility clearances for servicing...

Страница 5: ...or thermostatic remote control Wall mount thermostat wireless wall mount thermostat Decorative screen doors in various styles and finishes Decorative full door shrouds in various styles and finishes...

Страница 6: ...8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print no less the one half inch 1 2 in...

Страница 7: ...latch glass frame assembly 3 Millivolt board with burner cover 4 Log set see page 22 5 150 CFM fan kit 6 Co linear air duct 911XXL only Figure 6b Figure 6a FIREPLACE DIMENSIONS DESCRIPTION Height Wid...

Страница 8: ...tom shrouds may be ordered on a non returnable basis When ordering a custom shroud please specify existing fireplace front opening height and width Grill set required in various finishes purchased sep...

Страница 9: ...mney must be comprised of one of the following Factory built chimney 8 203mm minimum inside diameter Masonry Chimney 6 x 8 minimum inside diameter Existing Chimney Height Minimum 11ft 3 35m Maximum 40...

Страница 10: ...insert is ever removed removal of rivets or screws is acceptable The refractory glass doors screen rails screen mesh and log grates may be removed from existing fireplace before installing this gas fi...

Страница 11: ...mounting stud has been provided on right side of fireplace to reposition speed control receptacle assembly if desired Incoming wiring 110V 120V Speed Control Receptacle Assembly Temperature Switch Mag...

Страница 12: ...tch or thermostat Attach appropriate connectors to wall switch thermostat wires and connect to top and bottom terminals marked TH TPTH on gas valve REMOTE CONTROL Follow instructions included with rem...

Страница 13: ...ny If not follow ANSI 223 1 Commonwealth of Massachusetts Installation must be done by a licensed plumber or gas fitter IMPORTANT The efficiency rating of this appliance is a product of thermal effici...

Страница 14: ...Duct Figure 13a Large Restrictor Bend tabs to approx 80 degree angles to create tension to hold itself in place when installed Remove tab s to create small restrictor Slide restrictor into exhaust pi...

Страница 15: ...f tapping screws provided To ensure an air tight seal additional sealant should be applied at the point of connection Combustion intake extension Apply a liberal bead of sealant provided around male e...

Страница 16: ...n installation manual included with chosen vent system 3 From inside existing fireplace opening CAREFULLY pull ropes down until 4 exhaust pipe and 3 combustion air intake if using full connection meth...

Страница 17: ...uct to insert by aligning two holes in insert top to studs on each side of 4 exhaust duct and four holes at back of insert to mounting studs at lower end of air duct Leveling legs 2 per side IMPORTANT...

Страница 18: ...st be electrically grounded and connected in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 Current Edition or the Canadian Electrical Code...

Страница 19: ...OUT SEALING GASKET LOCATED UNDER CONTROL BOARD IN PLACE 1 Place control board in firebox aligning holes in control board with mounting studs in firebox bottom Ensure sealing gasket in in place on fire...

Страница 20: ...ea side 3 Snap rocker switch into place on shroud 4 Slide one connector on each rocker switch wire to the rocker switch 5 Attach shroud to insert by placing tabs on left and right shroud pieces into s...

Страница 21: ...s from lower grill insert grill bolts through lower hinges on insert Attach and tighten nuts Snap On Off rocker switch into mounting hole as shown 1 Remove glass frame assembly Refer to page 9 if nece...

Страница 22: ...nside of insert Figure 21a OPTIONAL MASONRY PANEL INSTALLATIONS 1 Remove screws A 2 ea side securing masonry panels Figure 21b 2 Align holes in mounting brackets to corresponding holes in insert face...

Страница 23: ...og placement may affect flame appearance and cause excessive soot to build up on logs and glass Figure 22a PAGE 22 Left panel Right panel BC BB S424 S423 S421 AP1 X5 BL Position left and right bottom...

Страница 24: ...VALVE PILOT ASSEMBLY COMPONENTS ELECTRODE PILOT HOOD THERMOPILE THERMOCOUPLE VALVE TERMINALS GAS CONTROL KNOB PIEZO IGNITOR HI LO FLAME ADJUSTMENT KNOB ON OFF ROCKER SWITCH PAGE 23 Figure 23a...

Страница 25: ...NY OTHER APPLIANCE DUE TO HIGH SURFACE TEMPERATURES KEEP CHILDREN CLOTHING AND FURNITURE AWAY This appliance needs fresh air for safe operation and must be installed so there are provisions for adequa...

Страница 26: ...fireplace is initially lit condensation will appear on the glass this is normal in all gas fireplaces and will disappear after several minutes B Locate pilot follow metal tube from gas control Located...

Страница 27: ...off wall switch or adjust setting on thermostat or remote control NOTE The pilot will stay lit H Turn pilot off by pushing in and turning gas control knob to OFF DO NOT FORCE The gas control valve has...

Страница 28: ...ess rocker switch to OFF 7 Disconnect manometer hose and tighten screw clockwise Screw should be snug do not over tighten 8 Attach manometer to manifold pressure tap to verify it is completely sealed...

Страница 29: ...When fireplace is first lit the flames will be blue Flames will gradually turn yellowish orange during first 15 minutes of operation If flames remain blue or become dark orange with evidence of sootin...

Страница 30: ...s to approx 80 degree angles to create tension to hold itself in place when installed Remove baffle to expose venting FINALIZING THE INSTALLATION RESTRICTOR USAGE Turn fireplace on and allow to burn f...

Страница 31: ...talled with the heat dump in the closed position and will operate at its peak efficiency at this setting The heat dump may be opened as much as necessary to maintain desired heat level Remove glass fr...

Страница 32: ...G BEDDING MATERIALS ETC IT IS IMPERATIVE THAT CONTROL COMPARTMENTS BURNERS AND CIRCULATION AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN Annual examination of venting system by a qualified agency is...

Страница 33: ...INSTRUCTIONS A Check that pilot flame impinges on thermocouple Clean and or adjust pilot for maximum flame impingement B Ensure the thermocouple connection at gas valve is fully inserted and tight ha...

Страница 34: ...r connections are bad TROUBLESHOOTING BURNER WILL NOT LIGHT FREQUENT PILOT OUTAGES A Pilot shield not installed B Pilot flame too high or too low causing pilot safety to drop out Clean and adjust flam...

Страница 35: ...rizontal vent 1 4 6 mm rise per foot is required on horizontal venting E Inner vent pipe leaking exhaust gases back into firebox Check for leaks Repair if necessary F Improper vent cap installation Ch...

Страница 36: ...is not followed exactly a fire explosion or production of carbon monoxide may result causing property damage personal injury or loss of life The qualified service agency is responsible for proper ins...

Страница 37: ...t OCK S47A LP Gas Conversion Kit XXL 035 Burner Assembly Consult your dealer for information on optional accessories available for this fireplace This appliance tested certified by OMNI Test Laborator...

Страница 38: ...PAGE 37 LIMITED WARRANTY...

Страница 39: ...PAGE 38 LIFETIME WARRANTY...

Отзывы: