7.15.9.3 Global STO application example with KSM
The sample application below shows door guarding and emergency stop, controlled by a
safety control to switch the global STO-Enable inputs of an AKD-C device to SIL2, PLd. Both
drive strings are switched independently.
Kollmorgen KSM modules cannot be used.
For detailled application examples refer to the
Decentralized System Projecting Guide
.
7.15.9.4 OSSD test pulses
Safety controllers usually check their outputs periodically during the normal operation. These
test procedures create pulses to the STO-Enable inputs.
Test pulses with T1 < 300 µs and T2 > 200 ms will not have any influence to the safety rel-
evant STO function. Test pulses, which are outside of this specification, will switch the STO
function, but will not create a dangerous situation.