7.4 Fusing
Non renewable cartridge fuses must be used with finger safe fuse holders according to
IEC 60529.
7.4.1 External power supply fusing
US cartridge fuses
: Class CC or J, 600 VAC 200 kA, time-delay. The fuse must be UL and
CSA listed, UL recognized is not sufficient.
EU cartridge fuses
: types gS(gRL) or gG, 400 V/500 V, time-delay
Cartridge Fuses
Ampere rating
UL Region
CE Region
External AC power
supply fusing
20A (Time-Delay) example Bussmann:
LPJ20SP/DFJ20
example Siba:
type gS/gG, D02, 20A
External 24 VDC
supply fusing
15A (Time-Delay) example Bussmann:
LPJ15SP/DFJ15
example Siba:
type gS/gG, 15A
Cartridge fuse holders
:
Example Bussmann: CH Series Modular Fuse Holders, class J, 3 poles: CH30J3
Example Ferraz: Ultrasafe Fuse holders, class J, 3 poles: US3J3I
7.4.2 External regen resistor fusing
Cartridge Fuses
Ampere rating
UL Region
CE Region
AKD-C01007
25A
example Bussmann:
FWP-25A14F
example Siba:
type aR, 25A
Cartridge fuse holders
: example Bussmann, CH Series , class J, 3 poles: CH14J3
7.5 Ambient Conditions, Ventilation, and Mounting Position
Storage
Transport
Surrounding air tem-
perature in operation
0 to +40 °C under rated conditions
+40 to +55 °C with continuous current derating 4 % per Kelvin
Humidity in operation
Relative humidity 5 to 85%, no condensation, class 3K3
Site altitude
Up to 1000 meters above mean sea level without restriction
1,000 to max. 2,000 meters above mean sea level with power
derating 1.5%/100 m
Pollution level
Pollution level 2 as per IEC 60664-1
Vibrations
Class 3M1 according to IEC 60721-3-3
Environmental area
Cabinet IP 54 according to IEC 60529
Mounting position
Vertical
Ventilation
Built-in fan
The device shuts down in case of excessively high tem-
perature in the control cabinet. Make sure sufficient forced
ventilation is supplied within the control cabinet.
AKD-C Installation | 7 Technical description and data
Kollmorgen | kdn.kollmorgen.com | February 2018
31