AKD-C Installation | 3 Safety
3.3 Prohibited Use
Other use than that described in chapter “Use as directed” is not intended and can lead to per-
sonnel injuries and equipment damage.
The device may not be used
with a machine that does not comply with appropriate national directives or standards,
for driving elevators,
in applications with continuous, operational short circuits to the external regen resistor
contacts.
in applications with any short circuits to the DC-Bus link contacts.
The use of the device in the following environments is also prohibited:
potentially explosive areas
environments with corrosive and/or electrically conductive acids, alkaline solutions, oils,
vapors, dusts
ships or offshore applications
Wiring the system with hybrid cables from other manufacturers than Kollmorgen is not
allowed. Changing Kollmorgen cables or connectors is not allowed.
3.4 Warning notes placed on the product
Wait 7 minutes
after removing power
before servicing.
The minimum size of the protective earth
conductor shall comply with the local safety
regulations for high protective earthing
conductor current.
If these signs are damaged, they must be replaced immediately.
16
Kollmorgen | kdn.kollmorgen.com | February 2018