5.2 Conformance with EC Low Voltage and EMC Directives
EU Declarations of Conformity can be found on the Kollmorgen website.
Conformance with the EC EMC Directive 2014/30/EC and the Low Voltage Directive
2014/35/EC is mandatory for the supply of drives within the European Community.
The devices have been tested by an authorized testing laboratory in a defined configuration,
using the system components that are described in this documentation. Any divergence from
the configuration and installation described in this documentation means that the user will be
responsible for carrying out new measurements to ensure conformance with regulatory
requirements.
Kollmorgen declares the conformity of the product series AKD-C01007 with the following dir-
ectives:
EC Directive 2006/42/EC, Machinery Directive
Used harmonized standard EN13849-1 (2008)
EC Directive 2014/35/EC, Low Voltage Directive
Used harmonized standard EN61800-5-1 (2007)
EC Directive 2014/30/EC, EMC Directive
Used harmonized standard EN 61800-3 (2004)
The AKD-C01007 meet the noise immunity requirements to the 2nd environmental category
(industrial environment). For noise emission the AKD-C01007 meet the requirement to a
product of the Category C2.
These devices can cause high-frequency interferences in non industrial environments and
may require measures for interference suppression (such as additional external EMC filters).
5.3 Conformance with EC Machinery Directive, Functional Safety
Conformance with the EC Machinery Directive 2006/42/EC is mandatory for the supply of
safety components within the European Community. The STO safety implementation on the
AKD-N is certified by TÜV. The safety circuit implementation used for the safety function
"Safe Torque Off" in the drives is suited for SIL 2 according to IEC 62061 and PLd / CAT3
according to ISO 13849-1.
Safe Torque Off (STO) string type (global)
Structure
STO
ISO
13849-1
MTTF
d
IEC
62061
PFH
[1/h]
SFF
[%]
T
M
[Years]
AKD-C + 1 x AKD-N
global PL d, CAT 3
≥ 100
SIL 2
2.9E-08 97.08
20
AKD-C + 8 x AKD-N
global PL d, CAT 3
≥ 100
SIL 2
2.9E-08 99.44
20
Safe Torque Off (STO) single drive type (local)
Structure
STO
ISO
13849-1
MTTF
d
IEC
62061
PFH
[1/h]
SFF
[%]
T
M
[Years]
1 x AKD-N-DS/DT
local PL d, CAT 3
≥ 100
SIL 2
2.9E-08
97.12
20
See
AKD-N Installation Manual
for detailed information.
AKD-C Installation | 5 Approvals
Kollmorgen | kdn.kollmorgen.com | February 2018
23