3: Installation
3-24
UPS306-01-00 PowerWAVE 9000 DPA User Manual Dated 01-06-2010
Figure 3.19 External cabinet battery configurations
3.13 Multi-cabinet Parallel Communication Cables (Bus-lines)
In a multi-cabinet system a series of communication bus lines must be connected between each cabinet to
enable various parallel control functions to be carried out.
Communication BUS lines are connected as shown below
(See Figure 3.20)
.
Connect the parallel cabinet control cables
Note:
Refer to Figures 3.7 to 3.12 to identify the location of the components mentioned below.
1.
Fit a Parallel Adapter over the Connector JD8 on all UPS-cabinets.
Note:
The Parallel Adapter contains two connectors, JD5 and JD6 and a DIP switch (SW2)
(see Figure 3.20).
2.
Set DIP Switch SW2-2 on each Parallel Adapter depending on the UPS Cabinet in the parallel cabinet
configuration
3.
Connect PORT JD6 of the Parallel Adapter in Cabinet 1 to PORT JD5 of the Parallel Adapter in Cabinet
2 using the corresponding BUS-Cable (supplied).
4.
Connect PORT JD6 of the Parallel Adapter in Cabinet 2 to PORT JD5 of the Parallel Adapter in Cabinet
3 using the corresponding BUS-Cable (supplied).
5.
Continue in the same manner for the remaining UPS-Cabinets, as illustrated in Figure 3.20.
6.
In each cabinet, set DIP Switch SW2-2 on the Parallel Adapter according to the cabinet configuration, as
shown in Figure 3.20.
CAUTION: In DPA 10kVA, DPA 15kVA, DPA 20kVA, 30-50 12V-battery blocks are permitted
(even numbers only). In DPA 25kVA, DPA 30kVA and DPA 50kVA, 40-50 12V-battery blocks
are permitted (even numbers only). The correct number of battery blocks is set up on Control
Panel Menu: Service-Set-Up).
CBAT DPA-120
CBAT DPA-200
A
B
C
A
B
C
D
E
F
8
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
7
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
6
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
4
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
3
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
2
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
1
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
5x28Ah
(3x40)x28Ah (4x50)x28Ah
Key Point:
This section is required only if two (or more) cabinets are to be connected in a multi-
cabinet parallel configuration, as described paragraph 2.3.2.
WARNING:
Before making the following connections ensure that all the UPS cabinets are
powered down and each parallel isolator IA2 is open.
Содержание PW 9000DPA
Страница 1: ...User Manual Pioneering solutions for total power protection Kohler PW 9000DPA ...
Страница 2: ......
Страница 8: ...iv UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Страница 10: ...1 Safety 1 2 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Страница 18: ...2 Description 2 8 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Страница 76: ...7 Options 7 6 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Страница 85: ...UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 8 9 8 Specifications ...
Страница 86: ...8 Specifications 8 10 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...