UPS306-01-00 PowerWAVE 9000 DPA User Manual Dated 01-06-2010
3-1
3
Installation
3.1
Introduction
This chapter contains all the information necessary for the correct unpacking, positioning, cabling and
installation of the PowerWAVE 9000 DPA.
3.2
Receipt of the UPS
The UPS and accessories are delivered on a specifically designed pallet that is easy to move with a forklift or
a pallet jack.
The packing container protects the UPS from mechanical and environmental damage. This protection is
further increased by wrapping the PowerWAVE 9000 DPA UPS with a plastic sheet.
Upon receiving the UPS, carefully examine the packing container and the UPS for any sign of physical
damage. The outside 'Tip&Tel' (“FRAGILE” and “ARROW”) indicator should be intact if the equipment has
been transported in an upright position. In case of rupture (or if they are suspect) inform the carrier and
Kohler Uninterruptible Power immediately.
Ensure that the received UPS corresponds to the description indicated in the delivery note.
3.2.1 Site
transportation
If you transport the UPS equipment after it has been off-loaded (for example, for storage or moving to a
different installation location) please observe the following precautions.
WARNING:
All the operations described in this section must be performed by authorised
electricians or suitably qualified personnel.
Kohler Uninterruptible Power will take no responsibility for any personal or material damage
caused by incorrect cabling or operations, or activities which are not carried out in strict
accordance with the instructions contained in this manual.
CAUTION: When off loading the UPS always keep it in an upright position.
Do not drop the equipment.
Do not stack the pallets due to the high-energy batteries involved and the heavy weight.
CAUTION: Visible transport damages must be claimed to the carrier immediately after receipt!
Other claims for shipping damage must also be filed immediately and the carrier must be
informed within 7 days of receipt of the equipment.
Packing materials should be stored for further investigation.
CAUTION: Transportation:
To avoid the UPS cabinets and/or battery cabinet falling over, use the shipping brackets on the
rear and front to secure the cabinets.
– Do not tilt the cabinets more than 10° from vertical.
CAUTION: Potential dangers:
– If the cabinet has been tilted it might damage the equipment and it should not therefore be
connected to the mains electricity supply.
– The weight of the UPS system could cause serious injuries to persons or anything in the
surrounding area.
Содержание PW 9000DPA
Страница 1: ...User Manual Pioneering solutions for total power protection Kohler PW 9000DPA ...
Страница 2: ......
Страница 8: ...iv UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Страница 10: ...1 Safety 1 2 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Страница 18: ...2 Description 2 8 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Страница 76: ...7 Options 7 6 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...
Страница 85: ...UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 8 9 8 Specifications ...
Страница 86: ...8 Specifications 8 10 UPS306 01 00 PowerWAVE 9000 DPA User Manual Dated 01 06 2010 ...