Maintenance
Lubricants and operating fluids
Parameter
Unit
Method
Nitrate / Nitrite
-
EN 12014
pH value
-
EN/ISO 10523 ASTM D1287
Glycol
%
DIN 51375
Pour point
°C
°F
ISO 3016 ASTM D5985
Freezing point
°C
°F
ISO 3013 ASTM D1177
Bacteria
count
-
Additive elements
(B, Ba, Ca, K, Mg, Na, P, S, Si)
mg/kg
ppm
DIN 51399
Wear elements
(Al, Cr, Cu, Fe, Mg, Mo, Ni, Pb, Sn, Ti, V)
mg/kg
ppm
DIN 51399
Contamination
(Ca, Mg, Mo, Si, Sn, Zn)
mg/kg
ppm
DIN 51399
Corrosion copper
-
EN/ISO 2160
Corrosion steel
-
ISO 7120
Tab. 39: KD coolant analysis parameters
Keeping the cooling system clean
Usually, cleaning the cooling system is not necessary.
In case of contamination with bacteria, fungi or yeast, a mixture of fresh coolant added with
biocides is suitable. The following products are approved:
Manufacturer
Product-
name
Concentration
Packin
g
Order #
Schülke & Mayr Gmbh
Grotan WS
Plus
0.15% by volume Liquid
X00065326
(10 kg (22.05 lb))
Grotanol SR1
1% by volume
Liquid
X00057297
(10 kg (22.05 lb))
X00057298
(200 kg (441 lb))
Troy chemical company Troyshield
1% by volume
Liquid
-
Tab. 40: KD cooling system cleaners
If there is need for a full cleaning of the system, flush the entire system with adequate water,
then:
– Use the approved products to clean the system
.
– Use the approved products to clean the components
.
Manufacturer
Product-
name
Concentration
Packin
g
Order #
Kluthe
Hakutex 111
2% by volume
Liquid
X00065751
Hakupur
50-706-3
2% by volume
Liquid
X00055629
KD62V12 33521030301_8_1 EN_US 2022-09
© 2022 by Kohler Co. All rights reserved.
155
Содержание KD62V12
Страница 6: ...6 2022 by Kohler Co All rights reserved KD62V12 33521030301_8_1 EN_US 2022 09...
Страница 8: ...8 2022 by Kohler Co All rights reserved KD62V12 33521030301_8_1 EN_US 2022 09...
Страница 163: ...Operating faults Faults Cause Remedy KD62V12 33521030301_8_1 EN_US 2022 09 2022 by Kohler Co All rights reserved 163...
Страница 210: ...33521030301_8_1 EN_US 2022 09 LHID12566146 2022 by Kohler Co All rights reserved...