TP-6198 3/15
9
Safety Precautions and Instructions
Welding on the generator set. Can
cause severe electrical equipment
damage.
Before welding on the
generator set perform the following
steps: (1) Remove the battery cables,
negative (--) lead first. (2) Disconnect
all engine electronic control module
(ECM) connectors. (3) Disconnect all
generator set controller and voltage
regulator circuit board connectors.
(4) Disconnect the engine battery-
charging
alternator
connections.
(5) Attach the weld ground connection
close to the weld location.
Installing
the
battery
charger.
Hazardous
voltage
can
cause
severe injury or death.
An
ungrounded battery charger may
cause electrical shock. Connect the
battery charger enclosure to the ground
of a permanent wiring system. As an
alternative,
install
an
equipment
grounding
conductor
with
circuit
conductors and connect it to the
equipment grounding terminal or the
lead on the battery charger. Install the
battery charger as prescribed in the
equipment manual. Install the battery
charger in compliance with local codes
and ordinances.
Testing live electrical circuits.
Hazardous voltage or current can
cause severe injury or death.
Have
trained and qualified personnel take
diagnostic measurements of live
circuits. Use adequately rated test
equipment with electrically insulated
probes and follow the instructions of the
test equipment manufacturer when
performing voltage tests. Observe the
following precautions when performing
voltage tests: (1) Remove all jewelry.
(2) Stand on a dry, approved electrically
insulated mat. (3) Do not touch the
enclosure or components inside the
enclosure. (4) Be prepared for the
system to operate automatically.
(600 volts and under)
High voltage test.
Hazardous
voltage can cause severe injury or
death.
Follow the instructions of the
test equipment manufacturer when
performing high-voltage tests on the
rotor or stator.
An improper test
procedure can damage equipment or
lead to generator set failure.
Connecting the battery and the
battery charger. Hazardous voltage
can cause severe injury or death.
Reconnect
the
battery
correctly,
positive to positive and negative to
negative, to avoid electrical shock and
damage to the battery charger and
battery(ies).
Have
a
qualified
electrician install the battery(ies).
Short
circuits.
Hazardous
voltage/current can cause severe
injury or death.
Short circuits can
cause bodily injury and/or equipment
damage
.
Do not contact electrical
connections with tools or jewelry while
making
adjustments
or
repairs.
Remove all jewelry before servicing the
equipment.
Engine block heater.
Hazardous
voltage can cause severe injury or
death.
The engine block heater can
cause electrical shock. Remove the
engine block heater plug from the
electrical outlet before working on the
block heater electrical connections.
Electrical backfeed to the utility.
Hazardous backfeed voltage can
cause severe injury or death.
Install
a transfer switch in standby power
installations to prevent the connection
of standby and other sources of power.
Electrical backfeed into a utility
electrical system can cause severe
injury or death to utility personnel
working on power lines.
Moving Parts
Airborne particles.
Can cause severe injury or
blindness.
Wear protective goggles and clothing
when using power tools, hand tools,
or compressed air.
WARNING
Servicing the generator set when it
is operating. Exposed moving parts
can cause severe injury or death.
Keep hands, feet, hair, clothing, and
test leads away from the belts and
pulleys when the generator set is
running. Replace guards, screens, and
covers before operating the generator
set.
Heavy Equipment
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Do not use lifting eyes.
Lift the generator set using lifting bars
inserted through the lifting holes on
the skid.
WARNING
Hot Parts
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
WARNING
Содержание 15/30RES
Страница 2: ......
Страница 18: ...TP 6198 3 15 18 Section 1 Specifications Notes ...
Страница 62: ...TP 6198 3 15 62 Section 5 Component Testing and Adjustment Notes ...
Страница 71: ......