TP-6198 3/15
19
Section 2 Scheduled Maintenance
Section 2 Scheduled Maintenance
Hazardous voltage.
Will cause severe injury or death.
This equipment must be installed and
serviced
by
qualified
electrical
personnel.
DANGER
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
WARNING
Disabling the generator set. Accidental starting can
cause severe injury or death.
Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
Moving parts.
WARNING
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
WARNING
Servicing the exhaust system. Hot parts can cause
severe injury or death.
Do not touch hot engine parts. The
engine and exhaust system components become extremely
hot during operation.
Servicing the alternator. Hot parts can cause severe
injury or death.
Avoid touching the alternator field or exciter
armature.
When shorted, the alternator field and exciter
armature become hot enough to cause severe burns.
Risk of fire.
Can cause severe injury or death.
Do not smoke or permit flames or
sparks near fuels or the fuel system.
WARNING
Servicing the fuel system. A flash fire can cause severe
injury or death.
Do not smoke or permit flames or sparks near
the carburetor, fuel line, fuel filter, fuel pump, or other potential
sources of spilled fuels or fuel vapors. Catch fuels in an
approved container when removing the fuel line or carburetor.
Servicing the air cleaner. A sudden backfire can cause
severe injury or death.
Do not operate the generator set with
the air cleaner removed.
Gas fuel leaks. Explosive fuel vapors can cause severe
injury or death.
Fuel leakage can cause an explosion. Check
the LPG vapor or natural gas fuel system for leakage by using
a soap and water solution with the fuel system test pressurized
to 6--8 ounces per square inch (10--14 inches water column).
Do not use a soap solution containing either ammonia or
chlorine because both prevent bubble formation. A successful
test depends on the ability of the solution to bubble.