TP-6198 3/15
44 Section 4 Controller
4.9.2
Controller Configuration
The controller configuration for each generator model is
set at the factory and should not normally require
changes. The controller’s configuration mode allows
adjustment of the system parameters listed in this
section. Use the instructions in this section to check the
configuration after installation and change them to
match the settings shown in Figure 4-15, if necessary.
Parameter
Setting
Definition
Unit’s system voltage and frequency
Uu01
Single phase, 60 Hz, 120/240 VAC
Uu04
Three phase, 60 Hz, 138/277 or 240/480 VAC
Unit configuration
Uc01 *
Standby
Engine type
Ec03 *
15RYG/RES
Ec06 *
30RYG/RES
Engine data input types
See Figure 4-16.
Ed01 *
15/30RYG/RES
Ed02
15/30RYG/RES with Remote Digital Gauge
Battery voltage
Bt12 *
Battery voltage 12 VDC
Bt24
Battery voltage 24 VDC
Communications
Cn00 *
No CAN communications
Cn01
J1939 (use for Remote Digital Gauge)
* Factory settings.
Figure 4-15
Configuration Parameters
Parameter
Low Coolant Level Sensor
Pressure Sensor
Temperature Sensor
Magnetic Pickup
Ed00
Digital Switch
Digital Switch
Digital Switch
No
Ed01
Digital Switch
Digital Switch
Analog Sender
No
Ed02
Digital Switch
Analog Sender
Digital Switch
No
Ed03
Digital Switch
Analog Sender
Analog Sender
No
Ed04
Digital Switch
Digital Switch
Digital Switch
Yes
Ed05 *
Digital Switch
Digital Switch
Analog Sender
Yes
Ed06
Digital Switch
Analog Sender
Digital Switch
Yes
Ed07
Digital Switch
Analog Sender
Analog Sender
Yes
Ed08
Analog Sender
Digital Switch
Digital Switch
No
Ed09
Analog Sender
Digital Switch
Analog Sender
No
Ed10
Analog Sender
Analog Sender
Digital Switch
No
Ed11
Analog Sender
Analog Sender
Analog Sender
No
Ed12
Analog Sender
Digital Switch
Digital Switch
Yes
Ed13
Analog Sender
Digital Switch
Analog Sender
Yes
Ed14
Analog Sender
Analog Sender
Digital Switch
Yes
Ed15
Analog Sender
Analog Sender
Analog Sender
Yes
* Factory setting for replacement controllers. See Figure 4-15 for the default settings for certain models. The installation of optional sender
kits (available for some models) may require a different Ed setting.
Figure 4-16
Engine Data Input Types, Parameter Ed