NOVAR 2600 Operating Manual
Instrument Characteristics according to IEC 61557-12
power quality assessment function
PQI-S
classification according to par. 4.3
direct voltage connection
voltage connection via VT
SD
SS
temperature according to par. 4.5.2.2
K55
hu altitude according to par. 4.5.2.3
< 95 % - noncondensation conditions
< 3000 m
active power/energy function performance class
0.5
Outputs & Digital Input
Relays („R“-output type models)
type
N.O. contact
load rating
standard models
250 V
AC
/ 4 A
“H” models
250 V
AC
/ 4 A
110 V
DC
/ 0.5 A
220 V
DC
/ 0.2 A
Transistors („T“-output type models)
type
Opto-MOS
load rating
max. 100 V
DC
/ 100 mA
Digital Input
„R“-output type models
„T“-output type models
type
optoisolated, bipolar
maximum voltage
265 V
AC
( 460 V
AC
for overvolt. cat. II )
80 V
DC
/ 50 V
AC
voltage for “logical 0“ / “logical 1“
<= 30 V
AC
/ >= 90 V
AC
< 3 V
DC
/ > 10 V
DC
input power
( impedance )
< 0.4 VA
( Ri = 200 kΩ )
1 mA @ 10V / 5 mA @ 24V /
10 mA @ 48V
94