5.2.2.6.1 Info – General Window
•
Instrument Model
&
Serial Number
… Instrument hardware model & serial No.
•
Instrument Hardware, Firmware
&
Bootloader Versions
…Instrument hardware &
firmware specification.
•
Object Number
… Measured node specification ( preset by ENVIS program for data
identification ).
•
Vbatt
… backup battery voltage (if equipped).
•
Error Code
… Indicates some instrument's hardware or setting problem. At normal state
equals to 0. In case of detection of any error it contains a number in the range 1 ÷ 255
created as the sum of binary weights of up to eight possible causes. The following table
provides overview of them and recommended action:
Tab 5.2 : Instrument Errors
error No. weight
meaning
action
1
2
instrument setup error
set the instrument (optimally with the
ENVIS program, if possible) to the
default setting
; if the error appears
again send the instrument to a service
organization for repair
2
4
calibration error
the instrument must be recalibrated –
send to a service organization
4
16
RTC error
in
the time setup window
(or better with
the ENVIS program, if possible), set
actual date&time; if the error appears
again send the instrument to a service
organization for repair
7
128
archive data error
clear all of the archives with the ENVIS
program; if the error appears again send
the instrument to a service organization
for repair
5.2.2.6.2
Info – Archive Status
This screen is relevant for models with datalogging capability only.
At this submenu actual state of individual archive buffers can be checked. Detailed information of each
buffer can be viewed with the
button : actual record item pointer, total capacity of the buffer in
data record items and corresponding start and end date of the buffered archive are available.
At the last row actual number of internal flash memory bad sectors is displayed. During instrument's
lifetime some blocks (up to several tens ) of the memory can get wrong. The flash memory blocks are
permanently checked and in case of failure the wrong block is no longer used and replaced with a
spare block.
5.2.2.6.3 Info – Producer
At this submenu there is producer's logo and website URL-address only.
67
Содержание NOVAR 2600
Страница 82: ...NOVAR 2600 Operating Manual NOVAR 2600 T18 Typical Installation 82...
Страница 83: ...NOVAR 2600 Operating Manual NOVAR 2600 T7 Typical Installation 83...
Страница 87: ...NOVAR 2600 Operating Manual NOVAR 2600 T External Temperature Sensor Connection 87...
Страница 88: ...NOVAR 2600 Operating Manual NOVAR 2600 4 RS485 Remote Communication Connection 88...
Страница 89: ...NOVAR 2600 Operating Manual 8 Manufactured Models and Marking 89...