NOVAR 2600 Operating Manual
Then, in case that :
•
at least one valid output ( capacitor or choke ) was found
•
the instrument is not switched into the
manual
mode
•
no alarm action is active
•
voltage and current higher than measurable minimums at least in one of phases
the instrument starts to control power factor to preset value.
If the undercurrent (
I<
) alarm was disabled for the AOR-process to be able to pass without
any load in the network do not forget to reenable it back !!!
You can found detailed AOR process description in appropriate chapter below.
The instrument includes a row of other parameters – their description is stated in following chapters.
16
Содержание NOVAR 2600
Страница 82: ...NOVAR 2600 Operating Manual NOVAR 2600 T18 Typical Installation 82...
Страница 83: ...NOVAR 2600 Operating Manual NOVAR 2600 T7 Typical Installation 83...
Страница 87: ...NOVAR 2600 Operating Manual NOVAR 2600 T External Temperature Sensor Connection 87...
Страница 88: ...NOVAR 2600 Operating Manual NOVAR 2600 4 RS485 Remote Communication Connection 88...
Страница 89: ...NOVAR 2600 Operating Manual 8 Manufactured Models and Marking 89...