NOVAR 2600 Operating Manual
•
no alarm action is activated
If these conditions are met, the controller starts the AOR process :
•
automatically if the AOR parameter is set to
Auto
and the controller is in the control state
(i.e. it is not in the manual state); the process is automatically restarted each 15 minutes until
at least one compensation section with non-zero reactive power is recognized
•
if being launched manually with
the Run
command in the AOR setting
The AOR process is described in details in corresponding chapter below.
4.3.2.6 Manual Output Type & Power Filler
This is not any of controller parameters – it is a tool for easy manual mass setting of the compensation
sections' (outputs) types and powers.
If :
•
although recommended, the AOR process cannot be used for the sections recognition, and
•
all of the compensation sections are of the same type, and
•
the compensation sections powers are in any of the most usual ratios,
you can use
the manual output type & power filer.
Fig. 4.10 : Manual Filler
After entering the tool, in the window you can set the output type and minimum (nominal) output
reactive power (
O
MIN
), then select one of predefined output ratio and, finally, specify total number of
outputs.
When escaping the window, you must either confirm or cancel execution of the mass output setting.
If you confirm the execution, the controller checks the minimum output reactive power value (
O
MIN
) by
comparing it with the instrument measurement sensitivity. If the value entered is too low, the warning
message appears, for example :
The value is too low – minimum value is 6.5 kvar.
In such case all of the outputs' powers are cleared and you must enter a correct value again !
If the
O
MIN
value is correct, the controller fills preset number of outputs' types and powers, starting from
the output No. 1.1 up, with preset type and appropriate weight of power. Powers of the outputs
corresponding to weights 6 and higher are set to the same size as the weight 5. Both control and fixed
outputs are filled; only the outputs preset as alarm or fan/heater control are left unaffected.
35
Содержание NOVAR 2600
Страница 82: ...NOVAR 2600 Operating Manual NOVAR 2600 T18 Typical Installation 82...
Страница 83: ...NOVAR 2600 Operating Manual NOVAR 2600 T7 Typical Installation 83...
Страница 87: ...NOVAR 2600 Operating Manual NOVAR 2600 T External Temperature Sensor Connection 87...
Страница 88: ...NOVAR 2600 Operating Manual NOVAR 2600 4 RS485 Remote Communication Connection 88...
Страница 89: ...NOVAR 2600 Operating Manual 8 Manufactured Models and Marking 89...