NOVAR 2600 Operating Manual
The actual data group comprises other actual data presentations that are
accessible with the
button - so called
actual data display mode
switch
. When pressed, a pull up menu rolls over the display temporary.
By multiple pressing of the button a desired actual data subgroup can be
selected and displayed :
•
Actual values – values of all measured
quantities in numeric format.
•
Average values – average values of main
measured quantities including their maximums & minimums. For detailed description see
chapter
Display Average Values Evaluation and Aggregation
further below.
•
Waveforms – actual wave shapes of all measured voltages and currents.
•
Harmonics – actual harmonic components of all voltage and current signals
in both numeric and graphic ( histogram ) formats. For detailed description see chapter
Harmonics and THD Presentation.
•
Phasors – diagrams of voltage and current fundamental harmonic phasors. A
phase sequence can be checked here too (indicated as
1-2-3
or
1-3-2
).
With the last option of the display mode switch –
V,A,W↔%
– voltage, current and power quantities
expression can be switched between basic units and percent relative to preset nominal voltage
U
NOM
and nominal power
P
NOM
.
5.2.2.2 Daily and Weekly Graphs
This option is supported by instrument models equipped with RTC & additional memory
only.
A one-week history of main measured quantities ( such as voltages, currents, powers and power
factors ) is registered in the instrument's memory cyclic buffer. Individual courses can be displayed for
rough check ( for detailed check at a PC a main archive is intended, see appropriate chapters further
below ).
With the
button, either whole week or specified day of the passed
week can be selected – on the graph, the day is identified with its shortcut
( Mo = Monday, for example ). Excluding of seven passed days, so called
S-day and M-day can be viewed too.
The S-day is a predefined day of year. The S-day record refreshes once
per year only. The M-day is the day when maximum 15-minute average
value of
ΣI
occurred. Both the S-day date can be preset and the M-day
record can be cleared via communication link with ENVIS program only.
For details see the ENVIS program manual.
With the ►button desired group of quantities can be selected. For listing
through the selected group, use the ▲and ▼buttons.
5.2.2.3 Electricity Meter Data Group
The electricity meter group comprises registered electric energy and maximum active
power demand values. For detailed explanation see chapter
Energy Data Presentation
further below.
63
Fig. 5.5 : Actual Data
Display Mode Switch
Fig. 5.6 : Weekly Graph,
Daily Graph
Содержание NOVAR 2600
Страница 82: ...NOVAR 2600 Operating Manual NOVAR 2600 T18 Typical Installation 82...
Страница 83: ...NOVAR 2600 Operating Manual NOVAR 2600 T7 Typical Installation 83...
Страница 87: ...NOVAR 2600 Operating Manual NOVAR 2600 T External Temperature Sensor Connection 87...
Страница 88: ...NOVAR 2600 Operating Manual NOVAR 2600 4 RS485 Remote Communication Connection 88...
Страница 89: ...NOVAR 2600 Operating Manual 8 Manufactured Models and Marking 89...