NOVAR 2600 Operating Manual
The test can have up to six rounds with four testing steps each. After each step, the measurement
results of individual phases are analyzed. If the results of any phase is sufficiently stable, detected
current signal connection information is shown in the main line, as can be seen in the picture above in
the L1 phase result. The connection information can be one of following :
Tab. 4.6: CT Test Results
CT connection test
result
meaning
action required
correct connection
none (both phase and polarity correct)
R
correct phase,
reverse polarity
swap the current input wires
→
wrong phase,
correct polarity
move wires to
the next
phase current
input, keep the polarity
←
wrong phase,
correct polarity
move wires to
the previous
phase
current input, keep the polarity
R→
wrong phase,
reverse polarity
swap the wires and move them to
the
next
phase current input
R←
wrong phase,
reverse polarity
swap the wires and move them to
the
previous
phase current input
- - -
unsuccessful measurement recheck the connection
As soon as the connection detected at all of phase inputs, the CT test finishes. If all of current signals
connected correctly the test result looks like this :
Fig. 4.18 : CT Test Result – All of the Inputs Connected Correctly
Then you can close the window by pressing of any key, otherwise the window closes automatically
after one minute delay.
If the inputs are not connected correctly, the CT test result can look, for example, like this :
Fig. 4.19 : CT Test Result – the L2 and L3 Inputs Wrong Connected
In such case it is necessary to reconnect the current signals :
•
let the L1input unchanged
48
Содержание NOVAR 2600
Страница 82: ...NOVAR 2600 Operating Manual NOVAR 2600 T18 Typical Installation 82...
Страница 83: ...NOVAR 2600 Operating Manual NOVAR 2600 T7 Typical Installation 83...
Страница 87: ...NOVAR 2600 Operating Manual NOVAR 2600 T External Temperature Sensor Connection 87...
Страница 88: ...NOVAR 2600 Operating Manual NOVAR 2600 4 RS485 Remote Communication Connection 88...
Страница 89: ...NOVAR 2600 Operating Manual 8 Manufactured Models and Marking 89...