NOVAR 2600 Operating Manual
The value is taken in account during power factor control intervention evaluation in order the
contactors to be loaded as uniformly as possible.
•
Sw. On Time
…
the output switch-on time since the last clearing. The value is important for
connected compensation capacitor (if any) lifetime estimation. In case of the capacitor
replacement you can clear the counter by its editing and selection the
Clear
option.
The value is taken in account during power factor control intervention evaluation in order the
capacitors to be loaded as uniformly as possible.
•
Disch. Time Counter
…
actual time remaining to the output discharge in seconds (relevant
for capacitor character outputs only). The value is refreshed by preset
discharge time
(see
below) whenever the output is switched off. Until expired, the output is temporary blocked in
off-state and cannot by used by power factor control process.
To return back to the main PFC output setup group parameter list use the
button.
Tab 4.2 : PFC Output Setup – Overview of Parameters
Parameter
Setup Range
Default Setup
Comment
output No.1.1 ÷ 2.9 type,
nominal power and state
- type 0 / C / L / Z / alarm / fan /
heating
- power any
- state control / fixed-on / fixed-off
0 / 0 / control
Value corresponds to
U
NOM
specified.
discharge time (set1)
5 sec ÷ 20 min
20 sec
output set 2
0 / 1.2 ÷ 2.9
0
discharge time (set2)
5 sec ÷ 20 min
20 sec
Displayed when
output set
is set only.
switching mode
intelligent / linear / circular
intelligent
automatic output recognizer
(AOR) starting
auto / 0
auto
4.3.2.2 Discharge Time for Output Set 1/2
All of capacitor-character outputs are protected against early reconnection for preset discharge time
after being switched off. During this time, the control process lets such outputs off and even manual
attempts for closing such outputs are blocked.
As default,
the output set 2
parameter (see below for details) is off. Then,
the discharge time for
output set 1
is relevant only and used for all of outputs.
The discharge time for output set 2
parameter
is not displayed at all.
If
the set 2
parameter is active,
the discharge time for output set 2
parameter appears and can be set
and used for
output set
No. 2.
4.3.2.3 Output Set 2
With this parameter you can divide the controller outputs into two so called “sets”. Then some output
parameters can be specified individually for each of the sets.
As default,
the
Set 2
parameter is
Off
. In such case all of outputs are comprised into
set 1
and
the set
2
does not exists.
The output set 2
parameter can be set to any outputs from No. 1.2 up. If, for example, set to the output
No.
1.7
, two sets are defined :
•
set 1
comprises 6 outputs from No.
1.1
through
1.6
•
set 2
comprises outputs from
1.7
up, i.e. remaining (at maximum) 12 outputs No. 1.7
through 1.9 and 2.1 through 2.9
In other words
the set 2
parameter defines beginning output of the set 2.
33
Содержание NOVAR 2600
Страница 82: ...NOVAR 2600 Operating Manual NOVAR 2600 T18 Typical Installation 82...
Страница 83: ...NOVAR 2600 Operating Manual NOVAR 2600 T7 Typical Installation 83...
Страница 87: ...NOVAR 2600 Operating Manual NOVAR 2600 T External Temperature Sensor Connection 87...
Страница 88: ...NOVAR 2600 Operating Manual NOVAR 2600 4 RS485 Remote Communication Connection 88...
Страница 89: ...NOVAR 2600 Operating Manual 8 Manufactured Models and Marking 89...