MCKT - SUSPENDED MODULAR AIR CONDITIONING AND VENTILATION UNITS
OPERATION AND MAINTENANCE MANUAL
MCKT - SUSPENDED MODULAR AIR CONDITIONING AND VENTILATION UNITS
1. General Information
25
2. Technical Data and Use
25
2.1 Functional Systems
25
2.2 Dimensions
25
2.3 Compact and Modular Units
25
2.4 Airflow Rate Ranges
26
3. Construction of MCKT
26
3.1 Compact Units
26
3.2 Modular Units
26
3.3 Left- and Right-hand Side
26
4. Construction and Operation
of MCKT-HPM
26
4.1 MCKT-HPM Configurations
26
4.2 Heat Pump Operation Parameters
27
4.3 Construction of MCKT-HPM section
27
4.4 Cooling System Operation
27
4.5 MCKT Unit Operation with HPM Module
28
4.6 Limitations and Requirements
28
5. Transport, Storage
28
5.1 General Requirements
28
5.2 Transport of MCKT-HPM heat pump block
28
6. Installation of the Unit on Site
29
6.1 Location
29
6.2 Suspending the Unit
29
6.3 Connecting of ventilation ducts
30
6.4 Installation of the Bypass Damper Actuators
30
6.5 Setting the Anti-frost protection
30
6.6 Connecting heaters and coolers
30
6.7 Adjustment of Heater and Cooler Performance
31
6.8 Carrying Away Condensate
31
6.9 Power Connections
31
6.10 Electric heater
32
6.11 Fan Motor
32
6.12 Heat Pump Module
33
6.13 Control System
33
7. Preparing for First Start-up
33
7.1 Power Supply Installation
33
7.2 Filters
33
7.3 Water Heaters
33
7.4 Electric Heaters
33
7.5 Water and DX cooling coils
33
7.6 Cross-flow Counter-current Exchanger
33
7.7 Heat Pump Module
34
7.8 Fan section
34
8. Start-up of the Unit
35
9. Operation and Maintenance
35
9.1 Air Dampers
35
9.2 Filters
35
9.3 Heat Exchangers
36
9.4 MCKT-HPM Heat Pump Module
36
9.5 Silencers
36
9.6 Fan
37
10. Test Measurements
37
11. Occupational Safety and Health
(OSH) Manual
37
12. Information regarding Units
in MCKHT hygienic version
37
12.1 Lighting in Section
37
12.2 Inspection Openings (Portholes)
37
12.3 Filtration Materials
37
12.4
Trays
37
12.5
Casing
37
13. Service – Information
38
14. Start-up Report
39
TABLE OF CONTENTS
1. General Information
The subject matter of this study is the Operation and Main-
tenance Manual for the typeline of suspended modular air
conditioning and ventilation units type MCKT, manufac-
tured by KLIMOR S. A.
The purpose of the OMM [Operation and Maintenance
Manual] is to familiarise installers and users with the con-
struction, fitting, start-up as well as correct servicing and
operation of the unit. Prior to installing and operating the
unit, you should read through this Operation and Mainte-
nance Manual and follow strictly the guidelines and recom-
mendations contained herein.
The maintenance manual should always be near the unit
and be easily available to servicing personnel.
Non-compliance with the guidelines
and recommendations contained in the
Operation and Maintenance Manual
shall relieve the Manufacturer of war-
ranty-related liability.
2. Technical Data and Use
The MCKT Suspended Modular Air Conditioning and Venti-
lation Unit is designed for air conditioning and ventilation
systems, intake and outlet installations and with heat re-
covery for all types of public and private premises. Owing
to its height it has been designed to operate as a suspend-
ed unit. It operates with the use of outdoor and re-circu-
lated air. The source of power is electrical current; utilities:
heating/chilled water and Freon. The unit is manufactured
in the typeline of three sizes.
In standard version the unit is not designed
to operate in an environment of air tempe-
rature exceeding 45ºC and relative humidi-
ty of more than 60% and in an environment
endangered by the explosion of flamma-
ble gases and fumes that contain organic
solvents or other aggressive substances.
2.1 Functional Systems
Fitted with a set of functional modules, the unit enables
any air processing from the simplest air intake and outlet
to preparing intake air with regard to such parameters as:
• temperature: heating – water or electric heaters, cooling
– water or DX cooling coils
• air cleanness: preliminary and secondary filters
• noise level reduction – silencers
• heat recovery – counter-current cross-flow exchanger
with by-pass, heat pump.
Table No. 1
SAMPLE FUNCTIONAL CODES OF MCKT UNIT
MCKT01xxyyR(L)-PFVFSL
Simple air intake or outlet with
silencer
MCKT02xxyyR(L)-PFVFSL
MCKT03xxyyR(L)-PFVFSL
MCKT01xxyyR(L)-PFWH(EH)VFSF
Intake of air double treated and
heated up
MCKT02xxyyR(L)-PFWH(EH)VFSF
MCKT03xxyyR(L)-PFWH(EH)VFSF
MCKT01xxyyR(L)-PFWC(DX)VF
Intake of air treated and cooled down
MCKT02xxyyR(L)-PFWC(DX)VF
MCKT03xxyyR(L)-PFWC(DX)VF
MCKT01xxyyR(L)-PFCPRWH(EH)VF
Intake of air treated and heated up
with heat recovery and its outlet
MCKT02xxyyR(L)-PFCPRWH(EH)VF
MCKT03xxyyR(L)-PFCPRWH(EH)VF
The units may operate to intake, outlet air and in in-
take-outlet systems with heat recovery on a highly ef-
ficient counter-current exchanger with a performance
of up to 92% and on a heat pump. Moreover, they may
be fitted with silencer and secondary filtration sections.
As an option, they may be fitted with a mixing chamber
composed of two supplied air dampers located/assem-
bled on the channels.
2.2 Dimensions
Table No. 2
Dimensions
MCKT DIMENSIONS
SIZE
WIDTH
HEIGHT
MCKT 01 /CPR
661 / 1322
355
MCKT 02 /CPR
966 / 1932
355
MCKT 03 /CPR
966 / 1932
475
CONNECTION DIMENSIONS
SIZE
WIDTH
HEIGHT
MCKT 01
620
290
MCKT 02
925
290
MCKT 03
925
410
CPR – cross-flow exchanger block
Length of each section: 800mm
Length of cross-flow exchanger section: 1150mm.
2.3 Compact and Modular Units
With regard to the MCKT unit’s fittings, we can distin-
guish between two versions of the unit:
Compact Unit
– is made up of a single module with
a fan and a maximum of two air processing functions
(filtering and heating; filtering and cooling) – all units
in one casing with channel terminals and a shutoff air
dampers.