background image

34

35

www.klimor.com

www.klimor.com

MCKT - SUSPENDED MODULAR AIR CONDITIONING AND VENTILATION UNITS

OPERATION AND MAINTENANCE MANUAL

7.7   Heat Pump Module

First start-up of the system:

•  Carry out wiring of the unit according to attached dia-

grams,

•  Put the unit together and connect it to the system of air 

ducts,

•  Properly set the actuators on bypass damper and heat 

exchanger damper

•  Set the value in cross-flow h.e. pressure guage.
•  Programme the variable frequency drives for the fans,
•  Programme the variable frequency drive for the cooler 

compressor, 

•  Select application depending on the type of heater,
•  Adjust the unit’s airflow rate for the unit’s nominal per-

formance. The airflow rate both for intake and outlet has 
to be within a range acceptable for a given unit. Stand-
ard airflow rate should be set with the counter-current 
exchanger bypass damper closed. When adjusting the 
unit’s airflow rate, the circuit breaker responsible for the 
compressor’s operation should be disconnected. 

•  In case of reheater configuration, reduced airflow rate 

should be set appropriate for the defrost mode. For 
MCKT1-HPM it is 600 m

3

/h, while for MCKT2-HPM it is 

1000 m

3

/h. Adjustment must be done with the coun-

ter-current exchanger bypass damper open. When 
adjusting the unit’s airflow rate, the circuit breaker 
responsible for the compressor’s operation should be 
disconnected.

•  Prior to first start-up of the cooling system one should 

wait 3 h with switchgear power supply switched on and 
fans switched off. This will allow the heating element of 
the compressor casing to heat up the cooling oil appro-
priately. 

•  Switch on the compressor circuit breaker and start the 

system. Move on to the screen displaying the pressure in 
the cooling system. If after starting the compressor the 
pumping pressure does not rise and the suction pres-
sure does not drop considerably, this may evidence that 
the compressor’s power supply has not been connected 
properly. Incorrectly connected phases cause the motor 
to rotate in the wrong direction. After any two phases 
have been swapped the compressor will work properly.

•  The ratio of the amount of air at the intake to the amount 

of air at the outlet must be within the range from 0.5 to 1.4.

•  Following a correct test start, the assumed operation pa-

rameters may be set. The unit is fully ready for operation. 
Detailed information concerning the above activities is 
available in OMM re. control system.

7.8   Fan Section

Prior to start, it is necessary to make a thorough inspec-
tion of the fan section module. Make sure there are no 
objects in the vicinity of the fan that could enter the 
inside of the fan rotor. 
Check if the rotor turns without resistance (e.g. adja-
cent elements scraping against one another).

Prior to starting the motor it is necessary to check: 

•  the motor’s power connection (the voltage of the power 

supply network has to be the same as the voltage on the 
motor’s nameplate,

•  the condition of the earth wire between elements of the 

fan section and the unit’s casing,

•  the power cables inside the module must be firmly fixed 

to the elements of the construction so as to prevent 
them from getting close to movable elements (rotor),

•  the direction of the rotor’s revolutions (to be checked by 

impulse start of the motor) has to comply with the label-
ling on its casing. In case of non-compliance the direc-
tion of rotating supply power phases should be shifted 
by swapping any two phases in the terminal box,

•  setting of the inverters for fan start-up/warm-up time 

(should be a minimum of 30 sec.).

In order for the rotor to be able to rotate freely, make 
sure the slot between the rotor and the outlet nozzle 
is appropriate. 

The slot can be adjusted as follows:

•  loosen 6 bolts and move the outlet nozzle vertically,
•  move the rotor horizontally together with the motor, 

tray, load-bearing channel bars, vibration isolators, by 
loosening 4 bolts.

The slot size should be about 2.5mm. The distance 
the rotor is pulled onto the outlet nozzle should be 
2.5mm.

The slot should always be checked following transport 
of the device and its installation in the appropriate op-
erating position. 

2,5

2,5

A

A

NOZZLE

ROTOR 

NOZZLE POSITION 

ADJUSTMENT BOLT

UNIT 

POSITION 

ADJUSTMENT 

BOLT

DRAWING 19: 

Adjustment of the slot between the rotor and outlet nozzle.

 

RIVET 4

BOLT M6x16

NOZZLE

FAN R3G

HANDLE 

SCREW M6x16

BLINT RIVET NUT M6

SPRING WASHER   

DRAWING 20: 

Assembly of fan with EC motor

Continuous operation of the device with 

the inspection panels off is prohibited.

Having made all the checks, the unit’s inspection panels 
should be closed and the unit can be started up.
 

8.   Start-up of the Unit

Only qualified assembly personnel may carry 

out start-up operations.

The recommended time setting on the inverters for start-up/
warm-up of the fan is a minimum of 30s. 
Start-up of the unit should be commenced with the adjustment  
air damper shut at the inlet to the unit. Otherwise, with the air 
damper wide open, the motor may be overloaded resulting in 
durable damage. After the motor has been switched on, the 
adjustment damper should be opened gradually, and the fol-
lowing parameters should be regularly monitored:

•  the value of the intensity of the power consumed by the 

motor,

•  the amount of air pumped in the installation (airflow rate).

If the unit is fitted with an control system, the opening of 
the air damper by the servomotor should be controlled. As  
a rule, the intensity of the power consumed by the motor 
should not be greater than the rated value, given the assumed 
available amount of air and pressure. 
When the fan is in operation, one should listen out for any wor-
rying, unnatural metallic noises or whether the unit’s vibrations 
are not too heavy. 
After 30 minutes the unit should be switched off and the follow-
ing fittings should be inspected:

•  filters (if they have not been damaged),
•  drip trays and traps (appropriate condensate drainage),
•  fan section (temperature of motor and fan bearings – 

also the slot between the nozzle and the fan rotor).

In units with secondary filters, start-up is recommended 
without this filters cartridge installed. After start-up, it is 
recommended to clean preliminary filters. 

The antifreeze thermostat should be checked for correct op-
eration in temperature of air flowing into the water heater of 
not much less than the thermostat setting – e.g. 1-2ºC. Then, 
during operation of the unit the thermostat should be checked 
for correct operation by shutting the inflow of heating water for  
a moment. 
Assessment of the correct operation of the MCKT unit and the 
air conditioning and ventilation installation (system validation) 
may be issued after careful adjustment of the operation param-
eters and after obtaining correct air parameters in the premises, 
assumed by the design.  
The above-mentioned check operations should be done before 
the MCKT unit is commissioned. 

When the MCKT unit is started up for the first 

time, the Assembly and Start-up Report sho-

uld be filled in. The Report is in the form of an 

annex to the Warranty and in p.14 of this OMM 

9.   Operation and Maintenance

The MCKT unit is designed for continuous operation. Peri-
odic overhauls of the unit are warranty required. Filters are 
to be renewed by the user himself. 

Operation and maintenance works have been present-
ed below. 

Maintenance and servicing operations can 

only be carried out when the unit is off and 

not working.

9.1    Air Dampers

Air dampers, especially on the side of outside air, must 
be kept clean. Excess contamination may cause the 
blades to remain ajar or the rotating mechanisms to 
seize. 
Air dampers may be cleaned with an industrial vacu-
um cleaner with a soft suction nozzle, blown through 
with compressed air or washed with water under 
pressure and cleaning agents that do not cause alu-
minium corrosion. 

9.2   Filters

MCKT units make use of G4 or M5 sectional filters 
50mm in thickness as preliminary filters and M5÷F9 
bag filters as secondary filters. 
Filters should be renewed when the admissible pres-
sure drop on the filters has been exceeded (Table No. 
6) or according to visual inspection. The unit must be 
switched off during filter renewal. The class of new fil-
ters has to correspond to the class of the used filters. 
During filter renewal also the filtration section has to 
be cleaned. 
Operation of the units is allowed only with the filters on.

Table No. 7

 Filter Dimensions

MCKT FILTER DIMENSIONS AND SIZES 

Unit Size

G4/M5 Preliminary 

Cassete Filter

M5÷F9 

Secondary Bag Filter

W  x H

Amount

W  x H

Amount

MCKT01

610x305 

1

592x287

1

MCKT02

915x305

1

592x287
287x287

1

MCKT03

915x425

1

592x407
287x407

1

Содержание MCKT

Страница 1: ...NICZNO RUCHOWA OPERATION AND MAINTENANCE MANUAL PAGE 22 Suspended modular air conditioning and ventilation units MCKT 42 DTR MCKT 02v 5 2018 KLIMOR zastrzega sobie prawo do wprowadzania zmian KLIMOR r...

Страница 2: ...acyjna podwieszana DOKUMENTACJA TECHNICZNO RUCHOWA WERSJA POLSKA KLIMOR zastrzega sobie prawo do wprowadzania zmian zaawansowane rozwi zania klimatyzacyjne iwentylacyjne SERWIS SERVICE 4858 7839950 51...

Страница 3: ...ew MCKT02xxyyR L PFCPRWH EH VF MCKT03xxyyR L PFCPRWH EH VF Centrale mog funkcjonowa jako nawiewne wy wiewne oraz w zestawach nawiewno wywiewnych z odzyskiem ciep a na wysoko sprawnym wymienniku przeci...

Страница 4: ...wykonania Centrale podwieszane MCKT wykonywane s w wyko naniu prawym i lewym Stron wykonania definiowana jest usytuowaniem kr c w wymiennik w w odniesie niu do zwrotu przep ywu powietrza WYKONANIE LE...

Страница 5: ...a od 20oC do 40oC otoczenie pozbawione py w gaz w i par r cych oraz substancji aktywnych chemicznie o dzia aniu powodu j cym korozj 5 2 Transport bloku pompy ciep a MCKT HPM Ze wzgl du na mocowania el...

Страница 6: ...ych po winno realizowa prac w uk adzie prze cipr dowym W przeciwnym wypad ku wyst pi zmniejszenie u rednionej r nicy temperatur czynnika w wymienniku i przep ywaj cym powietrzu a w konsekwen cji spade...

Страница 7: ...o nagrzewnic wodnych oraz termostat zapobiegaj cy przed przegrzaniem w nagrzewnicach elektrycznych Elementy te realizuj funkcj zabezpieczaj ce jedynie wsp pracuj c o od powiednim uk adem automatyki Ws...

Страница 8: ...w wentylatora sprawdzi poprzez w czenie impulsowe silnika musi by zgodny z oznacze niem na jego obudowie W przypadku niezgodno ci nale y zmieni kierunek wirowania faz napi cia zasilaj cego poprzez za...

Страница 9: ...od z detergentem niepowoduj cym korozji aluminium lub p ukanie strug wody pod du ym ci nieniem dla znacznych zabrudze Podczas wszystkich czynno ci nale y post powa ostro nie by nie zniekszta ci p yt a...

Страница 10: ...2 2 Wzierniki inspekcyjne bulaje Wzierniki inspekcyjne bulaje o rednicy 200mm s zamontowane w pokrywach sekcji w kt rych wyst puje o wietlenie Umo liwiaj one bez wy czania centrali ocen stop nia zabru...

Страница 11: ...ww klimor pl www klimor pl MCKT MODU OWA CENTRALA KLIMATYZACYJNA PODWIESZANA DOKUMENTACJA TECHNICZNO RUCHOWA MCKT MODU OWA CENTRALA KLIMATYZACYJNA PODWIESZANA DOKUMENTACJA TECHNICZNO RUCHOWA NOTATKI N...

Страница 12: ...wis klimor pl MCKT Suspended modular air conditioning and ventilation units OPERATION AND MAINTENANCE MANUAL ENGLISH VERSION KLIMOR reserves the rights to introduce alteration without prior notice adv...

Страница 13: ...ontained in the Operation and Maintenance Manual shall relieve the Manufacturer of war ranty related liability 2 Technical Data and Use The MCKT Suspended Modular Air Conditioning and Venti lation Uni...

Страница 14: ...spended units are manufactured as left and right hand sided The side version is defined with re gard to the location of the exchanger joints in relation to airflow return LEFT HAND SIDED VERSION RIGHT...

Страница 15: ...active substances with corrosive properties 5 2 Transport of MCKT HPM heat pump module Owing to the fastening of the cooling installation ele ments operation long lasting transport and storage is una...

Страница 16: ...ch to hold the joint The hy draulic installation and exchanger connection should allow their unrestrained disconnection and removal from the unit for the purposes of repair or maintenance Connecting t...

Страница 17: ...All information is included in OMM re control system 7 Preparing for First Start up Only appropriately qualified and trained installation and start up team can perform first start up of the unit afte...

Страница 18: ...A NOZZLE ROTOR NOZZLE POSITION ADJUSTMENT BOLT UNIT POSITION ADJUSTMENT BOLT DRAWING19 Adjustmentoftheslotbetweentherotorandoutletnozzle RIVET4 BOLTM6x16 NOZZLE FANR3G HANDLE SCREWM6x16 BLINTRIVETNUT...

Страница 19: ...sure Ranges for MCKT HPM PARAMETER MIN MPa MAX MPA Low Pressure 0 25 0 65 HighPressure 1 1 2 5 9 5 Silencer The silencer section is fitted with slotted levers filled with non flammable mineral wool an...

Страница 20: ...the unit is available at the Service Department Fax 48 58 783 98 88 Tel 48 58 783 99 50 51 Cell Ph 48 510 098 081 E mail serwis klimor pl 14 Start up Report DATE PLACE FORENAME AND SURNAME OF PERSON...

Страница 21: ...40 41 www klimor com www klimor com MCKT SUSPENDED MODULAR AIR CONDITIONING AND VENTILATION UNITS OPERATION AND MAINTENANCE MANUAL NOTES NOTES...

Страница 22: ...SERWIS SERVICE 4858 7839950 51 48 510098081 serwis klimor pl MCKT KLIMOR ru...

Страница 23: ...e i freonowe 55 7 6 Wymiennik krzy owo przeciwpr dowy 55 7 7 55 7 8 56 8 56 9 57 9 1 57 9 2 57 9 3 58 9 4 58 9 5 59 9 6 59 10 59 11 59 12 60 12 1 60 12 2 60 12 3 60 12 4 60 12 5 60 13 60 14 61 1 M MCK...

Страница 24: ...MCKT 03T 03 1200 5200 3 MCKT 03 1200 4200 3 3 3 1 25 0 8 U 3x230 400V 50Hz MCKT01 02 03 EC 0 10V MCKT01 02 03 MCKT MCKT 3 2 MCKT G4 M5 FS50 M5 F7 F9 4xM6 4xM6 3 3 MCKT 01 4 4 1 02 03 4 2 4 MCKT01 HPM...

Страница 25: ...com www klimor com 4 3 1 12 11 2 10 10 7 8 4 4 6 9 5 3 3 04 1 2 3 4 5 6 7 8 9 10 11 12 13 4 4 O 4 5 4 5 1 5 C 5 C 0 4 5 2 4 6 4 5 5 1 MCKT MCKT 80 20 C 20 C 40 C 5 2 05 05 90 06 06 6 6 1 500 6 2 6 2...

Страница 26: ...8M8 07 MCKT 6 2 2 Mo M6x60 6 60 M6x60 08 MCKT M M6 16 09 M6 70 09 09 MCKT CPR 6 2 3 6 16 6 6 10 CPR CPR 6 16 10 6 3 MCKT A B B A 6 70 6 6 6 110 6 4 3 4 MCKT1 HPM 1 2 3 4 RYS 11 MCKT1 HPM 1 2 1 2 1 1 2...

Страница 27: ...52 53 ru ru MCKT www klimor com www klimor com C 13 14 6 7 6 8 50 mm 60 mm Pa 50 mm Pa X 0 1 10 15 50 mm 60 mm Pa 50 mm Pa X 16 6 9 6 10 1 2 3 65 75 C 25K 6 11 30 E E CBE U 17 18...

Страница 28: ...11 12 13 1 12 0 10 8 _ 13 1 10V 10V n max 1V n min 1V n 0 13 8 10K 12 6 EC Lp Nr przew Przezn Kolor Funkcja 1 1 2 PE 1 3 N 1 5 L 1 6 NC 1 250 2 A 10 A 1 7 COM 2 2 8 0 10V 0 10 Ri 100k 2 10 RSB RS485 M...

Страница 29: ...2 5 2 5 2 5 2 5 A A C 19 4 M6X16 K R3G M6x16 M6 C 20 a EC 8 30 30 1 2 O MCKT MCKT MCKT www klimor com 9 MCKT 9 1 9 2 MCKT G4 M5 50 F5 M9 5 8 MCKT G4 M5 M5 F9 x x MCKT01 610x305 1 592x287 1 MCKT02 915...

Страница 30: ...58 59 ru ru MCKT www klimor com www klimor com 9 3 4 4 50 0 9 4 w 3 7 9 M M a M M A 0 25 0 65 1 1 2 5 9 5 9 6 10 11 1 2 3 4 5 6...

Страница 31: ...MCKT www klimor com www klimor com 12 MCK T MCKT DIN 1946 4 12 1 LED 12V LED 12 2 200 12 3 1 2 12 4 12 5 RAL 9010 13 48 58 783 98 88 T 48 58 783 99 50 51 48 510 098 081 E mail serwis klimor pl www kl...

Страница 32: ...62 63 ru ru MCKT www klimor com www klimor com...

Страница 33: ...dpowiedzialno ci 81 035 Gdynia ul Boles awa Krzywoustego 5 tel 48 58 783 99 99 e mail klimor klimor pl KLIMOR zastrzega sobie prawo do wprowadzania zmian KLIMOR reserves the rights to introduce altera...

Отзывы: