background image

Varisol Installation Manual

16

The pump may only be run when the system has 

been filled as dry operation will damage the pump. 

The desired flow rate is 1 litre per minute per m

²

 

(10 tubes=1m

²

).

1.   Set the pump to the first speed and run it 

manually from the controller (see following 

paragraph).

2.   If the desired flow rate is exceeded, set the 

flow meter to the desired rate by adjusting the 

isolating valve with a flat headed screwdriver 

(see diagram) with the pump running. Otherwise 

repeat this step at the next pump speed and 

continue until the desired flow rate is achieved

3.  Stop the pump.

 

Operating the pump in ‘Manual’ mode

(for SC range controllers)

In order to run the pump in ‘Manual’ mode, slide 

the operating switch on the left side of the solar 

control panel to the upper of the three positions. 

On the screen, select the appropriate relay with 

the up/down arrows and press the ‘Set’ button to 

run the relay and to switch it off again.

Other Relays

If any additional relays are set up on the system, these should be tested in ‘Manual’ mode as 

above, to ensure the connections have been wired correctly.

Decommissioning the System

Due to temperatures potentially exceeding 170

˚

C and pressures greater than 6 bar, a solar 

installation should only be decommissioned by a trained individual. The system should be 

decommissioned in low light, ideally in the morning when the solar loop should be coolest.

Disposal

Dispose of separate materials in accordance with local regulations. Please see the following 

pages for details of materials used in the construction of Thermomax collectors and guidance 

on disposal of antifreeze.

1. Electrical

• Isolate controller from mains

•  Remove cables to consumer units i.e. 

controller and pump 

• Remove sensors and associated cables

• Remove earthing cables

2. Collector Loop

• Beware of hot transfer fluid

•  Drain collector loop at drain valve. Contain the 

heat transfer fluid for appropriate disposal.

• Disconnect pipes from the manifold

3. Varisol Collector Disassembly

•  Remove M8 bolt from manifold support rail on 

the right hand end of the rail.

• Unclip rubber retainer on the tube support

•  Slide the Varisol removal slide along the 

manifold support rail strating at the right       

hand end.

•  Rotate each tube individually through 50

˚

 until 

engagement arrows line up and pull one tube 

from the rest of the assembly. Ensure tube is 

supported; only apply force onto the manifold 

to disengage.

• Repeat process until all tubes are removed.

Setting the flow rate

ISOLATING VALVE

Left side view of controller

OPEN CLOSED

Содержание Varisol

Страница 1: ...Renewables Installation Manual...

Страница 2: ...alling Tubes 7 Attaching the connection kit 9 Pump station 12 Safety vessel connections 13 Wiring the control panel 14 Commissioning the system 16 Decommissioning the system 17 Recycling Information 1...

Страница 3: ...idance Tube boxes should be transported horizontally Heavy goods should not be loaded on top of the kit boxes Care should be taken when opening boxes to prevent scratches or sudden shocks to the glass...

Страница 4: ...ts Flexi Connections Cooling Vessel DF100 only Expansion Vessel Tyfocor LS Connection Kit Tubes Insulated Hose Mounting Set Solar Roof Flashing 22mm 3 Port Diverter Valve Note 15 28mm also available 2...

Страница 5: ...21 5 300 22 35 6 360 22 53 7 420 22 80 8 480 22 110 9 540 22 153 Collector Area m2 Varisol Collector Expansion Vessel Sizing System Volume Ltr Expansion Vessel Size Ltr Cooling Vessel Size Ltr Static...

Страница 6: ...or tubes and be difficult to flush out Airlocks in the pipes will stop circulation through the system When the collector is orientated correctly i e with the manifold slightly higher than the base of...

Страница 7: ...d collector the available rafter spacing should be considered when sizing the collector to ensure that an appropriate side rail spacing can be achieved Roof Kit Sizing 05 Collector Number of Kit Type...

Страница 8: ...ackets C to roof using M8x50 coachscrews E 3 Secure side rails A to lower brackets using M10x65 bolt assy Step Two 1 From upper end of each side rail slide 2 M8x16 bolt into position 2 Secure side rai...

Страница 9: ...upper and lower support rail to 90 bracket as shown below 07 Installing the first tube Step Four 1 Align first tube with end of support rail and push home by clicking into rail push on upper push poi...

Страница 10: ...otection is removed first Step Six 1 Rotate second tube parallel with first tube 2 Locate upper plastic enclosure and lower tube support clip in rail 3 Push home the upper and lower fittings into the...

Страница 11: ...F 5 Ensure clip F legs protrude out of bottom of enclosure 6 Complete and attach technical label I 7 Close lid and secure with screw E G A D F I Qty Tubes A B C D E F G H I Step Nine flow connection 1...

Страница 12: ...EX ALU PEX or GALVANISED TUBING OR FITTINGS SHOULD NOT BE USED UNDER ANY CIRCUMSTANCES Flexible Pipe Connections Flexible pipe connections are recommended to connect the manifold through the building...

Страница 13: ...pression fittings provided for direct copper connection C0784 Insulated Hose Stub Fitting When flexible stainless steel pipe is being used to connect to the pump station the insulated hose stub fittin...

Страница 14: ...upplied includes an appropriate corrugated hose and threaded connection to join the vessel to the pump station Temperature Reducing Vessel TRV Also known as a cooling vessel or stratification vessel t...

Страница 15: ...in core copper cable with a 0 75mm cross section The sensors supplied are 1 5 metres in length Sensor cables can be extended with twin core copper cable of 0 75mm diameter up to 50 metres and 1 50mm d...

Страница 16: ...i e for an east west panel array or a stagnation configuration requiring a second pump Caution Avoiding damage and malfunctions When connecting an external relay or contactor or when connecting a pump...

Страница 17: ...e above the flow meter to ensure all air and liquid passes through the fill centre to filter any air and contaminants 4 Run the fill centre pump to circulate the Tyfocor LS for approximately 20 minute...

Страница 18: ...ceeding 170 C and pressures greater than 6 bar a solar installation should only be decommissioned by a trained individual The system should be decommissioned in low light ideally in the morning when t...

Страница 19: ...ith water Propylene glycol is not harmful to aquatic organisms and is readily biodegradable however the disposal of the solution should be done in a responsible manner taking into consideration local...

Страница 20: ...ifreeze properties the system should be refilled with fresh Tyfocor LS It is recommended that the solar system is serviced annually by a qualified engineer and immediately if the system shows evidence...

Страница 21: ...111 177 287 177 287 266 430 137 137 137 137 206 206 8 8 to 20 20 Tube Collector Height Above Ground m 30 Tube Collector 10 Tube Collector 20 Tube Collector 30 Tube Collector Weight Per Foot kg 45 Wind...

Страница 22: ...pond with specification shall be notified to Kingspan Renewable Ltd within 7 days from the delivery date or where the defect was not apparent on reasonable inspection within a reasonable time after di...

Страница 23: ...21...

Страница 24: ...opment and improvement we reserve the right to alter and amend the specification as shown in this literature Kingspan Renewables Limited 180 Gilford Road Portadown Co Armagh Northern Ireland BT63 5LF...

Отзывы: