Varisol Installation Manual
11
10
Key
1 Drain connection
2 Fill connection
3 Flow meter
4 Isolating valve
5 Motorised pump
6 6 bar pressure relief valve
7 Expansion vessel connection
8 Pressure guage
9 22mm connections (x 4)
10 Temperature guage
11 Air separator
12 Insulated fascia
13 Pressure relief discharge point
8
13
The Kingspan Solar product range offers both a single stream and a
dual stream pump station. Each pump station is available in two flow rates,
2-12 litres/minute and 8-28 litres/minute.
The flow rate required on a system is typically 1 litre per minute, per square metre installed.
Therefore a 2-12 litre/minute pump station will be sufficient for systems up to 12m
²
.
Connections of flow and return pipe work to the pump station are made with the straight
compression fittings provided for direct copper connection.
C0784 – Insulated Hose Stub Fitting
When flexible stainless steel pipe is being used to connect to the pump station, the insulated
hose stub fitting is required to make the connection. The split ring within the fitting should be
removed and placed over the second rib of the flexible pipe. When the compression fitting is
tightened, the split ring will click twice as it positions itself and locks inside the fitting.
C0785 – Insulated Hose Clamp Ring
When the short flexible connection is being joined to stainless steel pipe work, the insulated
hose clamp ring is required to make the connection. The split ring within the fitting should be
removed and placed over the second rib of the flexible pipe. When the compression fitting is
tightened, the split ring will click twice as it positions itself and locks inside the fitting.
Pump Station
6
9
9
8
7
5
4
3
3
2
1
1
2
4
5
7
9
9
6
11
12
13
10
10
12