Commissioning
Maintenance Checklist
The Aeromax plus must be maintained on and annual
basis.
The basic requirements are:
External checks
Visually inspect all connecting pipework for any signs of
leaks
Check the integrity of pipework insulation
Clean heat exchanger on rear of external unit
Tasks
'SFRVFODZ
Comments / Notes
1. With the water supply turned off, remove the screen from the
strainer in the combination inlet valve and clean off any dirt
Annual Visit
2.With the water supply turned off and the hot water taps open, check
the expansion vessel charge pressure and top up as necessary
Annual Visit
3. With the water supply turned on, open the temperature relief valve
and then the expansion valve to check unrestricted discharge into
tundish. Check valves for freedom of movement and confirm that
the water stops and both valves reseat correctly. Check at a full bore
discharge from either valve that there is no back up or discharge over
the tundish.
Annual Visit
4. Check that the correct outlet pressure is being maintained by the
pressure reducing valve by recording the pressure at the terminal
fitting or the tapping provided on the combination inlet valve.
Annual Visit
5. Check and clean the heat pump circuit filter.
Annual Visit
6. Open the primary/heating system safety valve and check that it
discharges safely.
Annual Visit
7. Check and if necessary top up the concentration of the heating
system anti-freez
Annual Visit
8. Re-establish the primary/heating system pressure and disconnect
the filling loop.
Annual Visit
9. Check the primary/heating system pressure does not rise above
2.5 bar and the safety valve does not drip when the system is at full
temperature.
Annual Visit
10. Check and release any air from the primary/heating systems.
Annual Visit
11. Check correct rating and type of fuse is fitted on the electrical
supply.
Annual Visit
12. Check for the correct operation and temperature setting of the
thermostats.
Annual Visit
13. Check the operation of the motorised valves.
Annual Visit
Document ref A3917A-MS1.
Further copies of this document are available on request as email copies- please contact the customer service
department
Customer Name
Service Enginners Name
Address
Company
Tel No
Site Number
Tel No
Date of Inspection
70
Inside the Heat Pump
Check all electrical connections for tighness
Visual inspection for eitrher oil or water leaks
Check operation of unit with cover still removed
Cylinder
Albion AeroCyl and iteral heat pump controls.
Содержание AeroMax Plus KHP0038
Страница 2: ...2...
Страница 16: ...Water connections Typical Schematic for Radiator System 16...
Страница 17: ...Water connections Typical Schematic for Radiator System 17 No 2 port required if using with heat pump NOTE...
Страница 60: ...Spare Part List KHP0041 4kW KHP0038 6kW KHP0039 8kW 60...
Страница 62: ...Spare Part List KHP0040 12kW KHP0042 15kW 62...