Mimimum installation clearances in mm are shown in fig.2 (single installation) and fig. 3 (serial installation)
Note:
The height of the obstacle at both front and rear side should be lower than the height of the outdoor unit.
A B C D E
'
G H L
weight
KHP0041
908
821
326
350
87
356
466
40
60
56
KHP0038
908
821
326
350
87
356
466
40
60
58
KHP0039
908
821
326
350
87
356
466
40
60
68
KHP0040
908
1363
326
350
174
640
750
44
69
99
KHP0042
908
1363
326
350
174
640
750
44
69
124
Safety procedures Dimensions
!
CAUTION
t &OTVSFBEFRVBUFQFSTPOBMQSPUFDUJWFFRVJQNFOUJTVTFE
t &YUSBPSEJOBSZNBJOUFOBODFPQFSBUJPOTNVTUCFDBSSJFEPVU
by specially trained personnel.
Disconnect the mains power supply prior to any
maintenance operations or prior to handling any
internal parts of the unit.
CAUTION
t 5IJTFRVJQNFOUDPOUBJOTSFGSJHFSBOUUIBUNVTUCF
disposed of in a proper manner.
t 8IFOEJTQPTJOHPGUIFVOJUBGUFSJUTPQFSBUJPOBMMJGF
remove it carefully.
t 5IFVOJUNVTUUIFOCFEFMJWFSFEUPBOBQQSPQSJBUF
disposal centre or to the original equipment dealer for
proper environmentally compatible disposal.
!
!
Dimensions and Clearances
Specifications
KHP0041
KHP0038
KHP0039
KHP0040
KHP0042
4kW
6kW
8kW
12kW
15kW
Data at Condition 1: A 7db/6wb W30/35 (EN14511)
Nominal heating capacity kW
4.1
5.8
7.2
11.9
14.5
Power input kW
1.01
1.37
1.82
3.01
3.57
Current Input (A)
4.35
5.95
7.91
13.1
15.5
COP (kW/kW)
4.05
4.24
3.95
3.94
4.06
Eurovent class, heating
A
A
B
B
A
Data at Condition 2: A 7db/6wb W40/45 (EN14511)
Nominal heating capacity (kW)
3.9
5.8
7.4
12.9
14
Power input (kW)
1.22
1.90
2.32
4.26
4.36
Current Input (A)
5.3
8.26
10.1
18.5
18.9
COP (kW/kW)
3.2
3.06
3.18
3.03
3.21
Eurovent class, heating
A
B
B
B
A
Water pressure drop, kPa (Condition 1)
16
9.5
14.5
26
33
'BO1PXFS*OQVU L8 $POEJUJPO
0.09
0.09
0.099
0.191
0.19
'BO4QFFE 31. $POEJUJPO
680
680
680
710 - 730
780-820
Current Input (A) (Condition 1)
0.65
0.65
0.85
1.63
1.18
Sound power level, heating‡ dB(A)
62
62
64
67
68
Sound pressure level, heating‡ dB(A)
42
42
44
47
48
/PNJOBM'MPX3BUF MNJO
12
16.8
19.8
34.8
41.4
/PNJOBM'MPX3BUF MNJO 3BEJBUPST
8.0
9.8
10.8
21.0
31.7
.JOJNVN'MPX3BUF MNJO UPPQFSBUFøPXTXJUDI
5
8
8
8
8
.BYJNVN'MPX3BUF MNJO
15
20
25
40
50
Refrigerant Content (g) R410A
1195
1350
1810
2450
3385
Oil Type
Ester Oil VG68
Compressor Type
Rotary DC Inverter Technology
Net Water Volume (L)
0.8
0.8
1
2.3
2.3
Water Connections
1" ISO228 (BSP) Male
Maximum Water Pressure (kPa)
300
Product Category
(EN14511) – Packaged Monobloc.
Above data applies to new, clean heat exchangers
'BDUPSZEFGVMUTFUUJOHTGPSIFBUJOHBSF¡$øPXUFNQ5PBMUFSUIJTZPVXJMMCFSFRVJSFEUPQVSDIBTFUIFBEWBODFEDPOUSPMMFS
KHP0008
8
Содержание AeroMax Plus KHP0038
Страница 2: ...2...
Страница 16: ...Water connections Typical Schematic for Radiator System 16...
Страница 17: ...Water connections Typical Schematic for Radiator System 17 No 2 port required if using with heat pump NOTE...
Страница 60: ...Spare Part List KHP0041 4kW KHP0038 6kW KHP0039 8kW 60...
Страница 62: ...Spare Part List KHP0040 12kW KHP0042 15kW 62...