Auxiliary accessories connection
Signal for requesting an External Heat Source or Dehumidification
#FUXFFO1*/4BOE/PGUIFUFSNJOBMTUSJQ TFF'JH
there is an output (1ph ~ 230V, 2A max) that can be
programmed using the remote User Comfort Interface (see
the control manual, Installation Menu code 106).
when OAT < Temperature set in nui code 150 (but OAT >
temperature set in KHP0008 code 148). In this region HP
keeps working and backup heater turns on if set point on
water is not reached by 5°C (value can be set with KHP0008
CODE 152) for 10 minutes (value can be set with NUI CODE
151). Backup heater turns off when set point on water is
reached again.
IMPORTANT NOTICE :
In case of SHW activation (pins 13-15 closed) heat pump
will turn on and backup heater will turn off. This will happen
in both the above strategies.
WARNING :
In case of EHS installation, it is mandatory to install a
thermal switch on the water circuit to protect the system
from too high water temperatures. This protection item has
to be located downstream from the EHS.
Additional water circulator for Aeromax Plus
It is possible to connect an additional water pump through
the
pins 12 and N. It is managed in the following way:
If OAT > temperature set in KHP0008 code 148
The additional water pump activation depending on the
KHP0008 code 156
0/0''EFQFOEJOHPOUIFPVUEPPSVOJUXBUFSQVNQMPHJD
in case of SHW activation ADD WP is ON;
0/0''EFQFOEJOHPOUIFPVUEPPSVOJUXBUFSQVNQ
logic,
JODBTFPG4)8BDUJWBUJPO"%%81JT0''
If OAT < temperature set in KHP0008 code 148
The additional water pump activation depending on the
,)1DPEF BMXBZT0/BMXBZT0''PS0/
0''EFQFOEJOHPO&)4
21
External Alarm Input
0O1*/PGUIFUFSNJOBMTUSJQ TFF'JHBOBMBSNJOQVU
(dry contact) is available to force off the unit. When the
contact is closed (Pin 21 active) the whole system is turned
0'' 6OJU0''810''(.$BMBSNO¡8IFOUIFESZ
contact open the system turns ON and works in the last
configuration.
It is possible to use this feature connected with different
FYUFSOBMDPOUSPMTZTUFNTBOEPSTBGFUZEFWJDFT'PSFYBNQMF
in case of danger an external safety device could send an
output alarm signal to close the contact. So the outdoor
unit turns off and remains in that condition until the dry
contact is reopened
Terminal Strip Pin Layout
Aeromax Plus
Description
PIN
Signal
Limits
KHP0008 Installation Menu Code
Additional external temperature
probe
23 - 24
Input (NTC 3kΩ @25°C)
N.A.
126
Sanitary Water Request
13 - 15
Input (contact switch
quality >25mA@12V)
N.A. N.A.
.BYJNVN'SFRVFODZ3FEVDUJPO
Compressor
13 - 14
Input (contact switch
quality >25mA@12V)
N.A. N.A.
3-way valve
10 - 18 - N
Output 230Vac (18-N:
Power supply, 10 signal)
1 ph ~ 230V, 2A
N.A.
1- External Heat Source Request
4 - N
Relay Output Contact
1 ph ~ 230V, 2A
106 - 148 -150 -151 - 152 -154 -155
2- Defrost
1- Alarm
5 - N
Relay Output Contact
1 ph ~ 230V, 2A
147
2- Ambient temperature reached
1- Alarm + defrost
11 - N
Relay Output Contact
1 ph ~ 230V, 2A
107 - 108
2-Humidifier
1- Trace heater
12 - N
Relay Output Contact
1 ph ~ 230V, 2A
156 - 157
2-Additional WP
Alarm input
21
Input (contact switch
quality >25mA@12V)
N.A. N.A.
External Water Circulator
16 - N
Relay Output Contact
1 ph ~ 230V, 2A
N.A.
NORMAL / ECO Mode
8 - 3
Dry contact
N.A.
N.A.
Note: The maximum total instantaneous current must be less than 3.5A. In the case of loads with higher
absorbed current, it is necessary to drive the loads with relays to be inserted between the power supply of the
load itself and drive the relays from the terminal strip.
Содержание AeroMax Plus KHP0038
Страница 2: ...2...
Страница 16: ...Water connections Typical Schematic for Radiator System 16...
Страница 17: ...Water connections Typical Schematic for Radiator System 17 No 2 port required if using with heat pump NOTE...
Страница 60: ...Spare Part List KHP0041 4kW KHP0038 6kW KHP0039 8kW 60...
Страница 62: ...Spare Part List KHP0040 12kW KHP0042 15kW 62...