Installation
July 2018
4-2
06-237518-001
4-1.4
System Overview
The cylinders, stored in the bank, are individually connected to the manifold assembly. The
connection is made with high-pressure hoses and a manifold check valve, one for each
cylinder. The manifold check valves allow for removal of one or more cylinders from the
manifold without having a significant loss of Agent should the remaining cylinders be
discharged.
The system can be released electronically by a control panel sending a signal to the release
unit.
Note:
Release unit solenoids must be continuously powered during system discharge.
The system can be released manually by removing the locking pin and turning the wheel of the
master cylinder manual release unit in the direction of the arrow (clockwise).
Each cylinders can be equipped with a pressure gauge for low pressure monitoring. The
“master” cylinder will include a solenoid valve release unit. The pressure from the “master”
cylinder is channelled to valves on the slave cylinders, releasing their content. During a
discharge, the cylinders in the cylinder bank will be released almost simultaneously.
Figure 4-1. Single Area Cylinder Bank Arrangement
Table 4-1. Single Area Cylinder Bank Arrangement Components
Item
Description
1
Agent Cylinder
2
Valve
3
Release Unit
4
Slave Cylinder Gauge Assembly
5
Actuation Hose
6
Pilot Line Bleed Valve (on back side)
7
Discharge Hose
8
3/4” BSP Manifold Check Valve
9
Manifold Support
To Distribution
Pipe Work
1
2
4
5
7
6
8
9
3
Содержание 400 Series
Страница 2: ...Table i Revision History Revision Change Description AA Initial Release ...
Страница 16: ...July 2018 xiv 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 157: ...06 237518 001 A 1 July 2018 APPENDIX A SAFETY DATA SHEETS ...
Страница 188: ...July 2018 A 2 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 189: ......