Component Descriptions
06-237518-001
2-5
July 2018
2-3.3
Release Units
Release units connect to the gauge port of the primary cylinder and are used to release
the agent to the piping system. Release units can be electric operated only or
manual/electric. Depending on the control panel requirements, release units can be
purchased with pressure gauges using Normally Open or Normally Closed (When Under
Pressure) contacts.
Release units that include manual operation have a tamper proof seal on the operation pin.
Replacement seals are included in the Release Unit Service kit, P/N: 38-400001-010.
Note:
Release unit solenoids must be continuously powered during system discharge.
Figure 2-5. Release Unit
Part Number
Pressure
Rating
Operation
Contact
38-400001-001
200 Bar
Manual/Electric
Normally Open
38-400001-002
200 Bar
Manual/Electric
Normally Closed
38-400001-003
300 Bar
Manual/Electric
Normally Open
38-400001-004
300 Bar
Manual/Electric
Normally Closed
Содержание 400 Series
Страница 2: ...Table i Revision History Revision Change Description AA Initial Release ...
Страница 16: ...July 2018 xiv 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 157: ...06 237518 001 A 1 July 2018 APPENDIX A SAFETY DATA SHEETS ...
Страница 188: ...July 2018 A 2 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 189: ......