ELECTRICAL INSTALLATION
The cable routing plan shall include all electrical components including detailed loop
information and the cable quality to be used, such as; mm sq, rating IEC, braiding, twisted
cores, required material and colour of the outer sheath, bending radius, max. distance between
supports/strapping, 90º crossing etc.
Also the cable routing plan shall include notes regarding maximum distances allowed for
parallel runs, minimum distances between control and power cables (normally 500 mm), and
separate cable ways/trays to be used etc.
4-14.1
Release Unit/Slave Cylinder Gauge Assembly Wiring
Note:
Release unit solenoids must be continuously powered during system discharge.
Connect the release unit/slave cylinder gauge assembly as indicated on the electrical wiring
diagram and terminate in the allocated terminals in the control panel/junction box.
The release units are wired separately. The slave cylinder gauge assembly should be connected
in a single loop configuration (between cylinders) using the quick connect cable joiners
provided.
Figure 4-21. Quick Connect Wiring Example
Figure 4-22. Single Wiring Example (Not Valid for Systems Requiring Normally Open Connections)
Control Panel
-
1
+
2
3
4
-
1
+
2
3
4
-
1
+
2
3
4
-
1
+
2
3
4
End Terminal
Plug
(38-400005-101)
38-400005-102
or
38-400005-103
&
End of Line Resistor (EOL)
or
38-400005-100
38-400005-100
38-400005-100
38
-4
0
000
5-
10
5
Control Panel
-
1
+
2
3
4
-
1
+
2
3
4
-
1
+
2
3
4
-
1
+
2
3
4
Содержание 400 Series
Страница 2: ...Table i Revision History Revision Change Description AA Initial Release ...
Страница 16: ...July 2018 xiv 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 157: ...06 237518 001 A 1 July 2018 APPENDIX A SAFETY DATA SHEETS ...
Страница 188: ...July 2018 A 2 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 189: ......