General Information
06-237518-001
1-1
July 2018
CHAPTER 1
GENERAL INFORMATION
1-1
INTRODUCTION
The Kidde Fire Protection Inert Gas System(400 Series) (Kidde IGS) using IG-01, IG-55, IG-
100, or IG-541 (herein referred to collectively as the “Agent”) are designed to suppress fires
in specific hazards or equipment located where an electrically non-conductive Agent is required
and where Agent clean-up creates a problem.
These Agents are approved by the EPA, NFPA
and ISO for use in fire suppression systems. Use Kidde IGS as a total flooding system for
protection against hazards that are enclosed or for protecting equipment that includes an
enclosure within itself that will contain the Agent.
Key features of all the offered inert Agents are:
•
People safe with no restrictions for occupied areas up to and including 52% Agent concen-
tration.
•
Zero ozone depletion potential
•
Zero global warming potential
•
Atmospheric lifetime of zero days
•
Colourless, with low odour and no particulate or residue allowing for minimal business dis-
ruption after a discharge
•
Electrically non-conductive
For specific design concentrations see Section 3-3.
1-1.1
Use
Kidde IGS is used to extinguish fires in almost all flammable substances with only a few
exceptions. The Kidde IGS itself does not leave any hazardous substances after a release.
Cleaning up from the fire involves only repairing parts damaged by the fire; machine downtime
and other secondary damage can therefore be kept to a minimum.
The density of the Kidde IGS gases are similar to that of atmospheric air, therefore longer hold
times are expected as opposed to other heavier clean agents. The gases used in the Kidde IGS
are non-conductive and therefore suitable for the extinguishment of fires involving electrical
and electronic equipment.
The normal design concentrations used in Kidde IGS will result in an oxygen concentration
above 10% and thus are acceptable for protecting normally occupied enclosures.
Kidde IGS is also useful for extinguishing fires involving:
•
Flammable and combustible liquids
•
Sub floors and other concealed spaces
•
Delicate artefacts such as clothing, paintings, and other high-value items
•
In places where other extinguishing media could be directly destructive
Note:
Fires in solid materials (deep-seated) require that the design concentration is main-
tained for a sufficient period of time (hold time) to achieve total extinguishment.
Содержание 400 Series
Страница 2: ...Table i Revision History Revision Change Description AA Initial Release ...
Страница 16: ...July 2018 xiv 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 157: ...06 237518 001 A 1 July 2018 APPENDIX A SAFETY DATA SHEETS ...
Страница 188: ...July 2018 A 2 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 189: ......