TYPICAL WIRING DETAILS
Figure 4-23. Typical Wiring Details
4-16
INSTALLATION OF PRESSURE SWITCH, P/N 03-5713-0000
For single area systems the discharge pressure switches may be installed on the end of the
manifold, for multiple area systems a discharge pressure switch must be installed downstream
of each selector valve. All discharge pressure switches to be installed in a vertical orientation.
Follow these steps to install the discharge pressure switch in pipe work:
1. Install a tee piece where you want to install the discharge pressure switch.
2. Use bushings in the side outlet of the tee to reduce down to 1/4" BSP.
3. Install the adapter (P/N 15-8662-0041) into tee using PTFE thread tape on one side of the
adapter only.
4. Remove the tube connector from the pressure switch outlet.
5. Fit a flexible pilot hose (P/N 01-3272-1300) to the pressure switch outlet and the adapter.
WARNING
To prevent injury, de-energize all electrical components before installing the
pressure switch.
COIL
CONNECTION COIL UNIT PLUG
1
2
(3)
EOL
+
-
PANEL OUTPUT
JUNCTION BOX
SOLENOID CONNECTOR
-
PANEL OUTPUT
+
COIL
CONNECTOR 1 AND 2 FREE CHOSEN
CONNECTION COIL UNIT PLUG
SHIELD CONNECTOR
SOLENOID CONNECTION
24V DC SOLENOID CONNECTION TO NON REVERSIBLE VOLTAGE OUTPUTS:
24V DC SOLENOID CONNECTION TO REVERSIBLE VOLTAGE
MONITORING OUTPUTS
REFER TO PANEL SPECIFICATIONS FOR EOL TYPE/VALUE REQUIRED.
EOL AND DIODE TO BE POSITIONED CLOSE TO COIL.
IF A 4 PIN CONNECTOR IS AVAILABLE USE PIN 3.
Содержание 400 Series
Страница 2: ...Table i Revision History Revision Change Description AA Initial Release ...
Страница 16: ...July 2018 xiv 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 157: ...06 237518 001 A 1 July 2018 APPENDIX A SAFETY DATA SHEETS ...
Страница 188: ...July 2018 A 2 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 189: ......