PARAMETER MENU
FLOW FILTER
UP DOWN EXIT
P
FLOW FILTER 0-99.9s
1.00000
RIGHT UP EXIT
Use the keys “RIGHT” and “UP” to select the desired value and confirm with “P” or skip with “EXIT”.
The display returns to the setup parameter menu.
4.5.6.3 CUT
OFF
menu
In the submenu “CUT-OFF” the cutoff in percent of the full scale flow range can be set.
If the absolute value of the measured and filtered flow is below the cutoff value, the calculated flow is “0” and
consequently all outputs show zero flow and the total and batch value remain unchanged.
PARAMETER MENU
CUT OFF
UP DOWN EXIT
P
CUTOFF RATE (%)
0.5
RIGHT UP EXIT
Use the keys “RIGHT” and “UP” to select the desired value and confirm with “P” or skip with “EXIT”.
The display returns to the setup parameter menu.
4.5.6.4 RESP
STEP
menu
In the submenu “RESP STEP” the reaction to fast changing flows can be set.
If the difference between the measured flow and the filtered flow is smaller than the step response value, the flow
filter remains active. If the difference is higher than step response, the filter is cleared and filled with the new
value.
The recommended value for constant or slowly changing flow is 99% (the default value ex work). If the unit has to
react to fast changing flow, the optimum value depends on the individual situation. For ON / OFF operation a
value of half the ON flow is recommended.
NOTE:
A too low value will lead to noisy measurement whereas a too high value with fast changing flow (ON
/OFF operation) will lead to a too slow reaction of the meter.
PARAMETER MENU
RESP STEP
UP DOWN EXIT
P
RESPONSE STEP (%)
99.0
RIGHT UP EXIT
Use the keys “RIGHT” and “UP” to select the desired value and confirm with “P” or skip with “EXIT”.
The display returns to the setup parameter menu.
Содержание TRICOR TCE80 -E Series
Страница 1: ...Certified according to DIN ISO 9001 Manual TRICOR Coriolis Mass Flow Meter ...
Страница 2: ...SW Version Main V2 0x Display V2 0x Manual Revision 2 1 ...
Страница 90: ...Listings 90 Fig 22 Dimensions TCM5500 C through TCM65k C Fig 23 Dimensions TCM5500 E through TCM65k E ...
Страница 92: ...Listings 92 Remote meter Fig 24 Dimensions TCM A Remote wall mounted electronics Fig 25 Dimensions TCE8000 W ...
Страница 93: ...Listings 93 Fig 26 Dimensions TCE8000 E except A Fig 27 Dimensions TCE8000 E A ...
Страница 98: ...Contact Copyright KEM Subject to change without notice ES Rev 002 23 01 2012 ...