Manual Operation
64
4.5.7.4
CONTROL IN menu
In the submenu “CTRL IN” the control input can be configured.
The control input has 2 operating modes:
RESET BATCH:
If a high level is applied to the input, the batch counter is reset to 0.
This mode must be selected, if the control output is to be used as a batch output and / or if one of the analog
outputs is to be used as batch output
EXTERNAL ZERO:
If a high level is applied to the input, the TCE8000 starts the zero offset procedure.
IN/OUTPUTS MENU
CTRL INT
UP DOWN EXIT
P
CONTROL IN MENU
RESET BATCH
UP DOWN EXIT
Use the keys “UP” and “DOWN” to select the desired mode and confirm with “P” or skip with “E”.
If “EXT. ZERO” is selected and one of the outputs is set to batch output, the display shows
CHANGE FREQ OUT MODE
TO SELECT THIS
. OK
Confirm with “OK” and configure the output correspondingly if required.
4.5.7.5 INTERFACE
menu
In the submenu “INTERFACE” the interface can be configured.
Depending on the configuration one or more of the following interfaces can be selected:
RS485
HART
Foundation Fieldbus
IN/OUTPUTS MENU
INTERFACE
UP DOWN EXIT
P
SET INTERFACE MODE
RS485
UP DOWN EXIT
Use the keys “UP” and “DOWN” to select the desired mode and confirm with “P” or skip with “E”.
If “RS485” is selected, the display shows:
SET UNIT ADDRESS
01
RIGHT UP EXIT
Use the keys “RIGHT” and “UP” to select the desired unit address and confirm with “P” or skip with “EXIT”.
If an interface not implemented is selected, the display shows
Содержание TRICOR TCE80 -E Series
Страница 1: ...Certified according to DIN ISO 9001 Manual TRICOR Coriolis Mass Flow Meter ...
Страница 2: ...SW Version Main V2 0x Display V2 0x Manual Revision 2 1 ...
Страница 90: ...Listings 90 Fig 22 Dimensions TCM5500 C through TCM65k C Fig 23 Dimensions TCM5500 E through TCM65k E ...
Страница 92: ...Listings 92 Remote meter Fig 24 Dimensions TCM A Remote wall mounted electronics Fig 25 Dimensions TCE8000 W ...
Страница 93: ...Listings 93 Fig 26 Dimensions TCE8000 E except A Fig 27 Dimensions TCE8000 E A ...
Страница 98: ...Contact Copyright KEM Subject to change without notice ES Rev 002 23 01 2012 ...