Installation
40
Close the cable glands properly before applying power to the TCE80**!
WARNING!
The Ex d protection of the housing is void, if any of the cable glands is not closed properly!
Panel Mount Version
The supply terminals and the digital I/O terminals are rated for U
M
= 250V whereas the analog output and
interface terminals are rated for U
M
= 30V DC.
Connect the unit as described in chapter 3.2.3 ff. and chapter 3.3.5 to 3.3.7.
3.3.5 Power Supply and Grounding
For operation in hazardous areas a good connection of PE is mandatory. The cross section of the PE cable must
be at least the cross section of the supply cable or 1mm², whichever is higher.
The supply terminals (50, 51 for 24V DC or 90, 91 for mains operation) are designed for a rated voltage of 250V
AC.
WARNING!
Applying 250AC to the DC supply terminals (50, 51) will not affect the Ex safety of the TCE or TCM, but
will damage the supply circuit of the TCE!
The TCE80**-L-*B**-Ex can be connected to a 24V DC and a mains supply simultaneously. The unit will operate
properly as long as one of the 2 supplies is present.
For the circuit diagrams and the general description refer to chapter 3.2.4.
3.3.6 Digital Control Inputs and Outputs
The digital I/O terminals are designed for a rated voltage of 250V AC.
WARNING!
Applying 250AC to the digital I/O terminals (5, 6, 7, 8) will not affect the Ex safety of the TCE or TCM, but
will damage the I/O board of the TCE!
For the circuit diagrams and the general description refer to chapter 3.2.5.
3.3.7 Analog
Outputs
The analogue current output terminals are designed for a rated voltage of 30V AC.
The outputs are protected against wrong polarity. Voltages below 30V will not damage the outputs nor affect the
Ex safety.
WARNING!
Applying more than 30V DC to any of the outputs will damage the TCE and destroy the protection of the
TCM!
WARNING!
If more than 30V have been applied to any of the analog output pins, the unit must be returned to KEM
for repair as the safety barrier might be destroyed!
For the circuit diagrams and the general description refer to chapter 3.2.6.
Содержание TRICOR TCE80 -E Series
Страница 1: ...Certified according to DIN ISO 9001 Manual TRICOR Coriolis Mass Flow Meter ...
Страница 2: ...SW Version Main V2 0x Display V2 0x Manual Revision 2 1 ...
Страница 90: ...Listings 90 Fig 22 Dimensions TCM5500 C through TCM65k C Fig 23 Dimensions TCM5500 E through TCM65k E ...
Страница 92: ...Listings 92 Remote meter Fig 24 Dimensions TCM A Remote wall mounted electronics Fig 25 Dimensions TCE8000 W ...
Страница 93: ...Listings 93 Fig 26 Dimensions TCE8000 E except A Fig 27 Dimensions TCE8000 E A ...
Страница 98: ...Contact Copyright KEM Subject to change without notice ES Rev 002 23 01 2012 ...