KC-P30
Configuration
Installation manual V3.28
40
© KEBA
DIP switch
Function
Illustration
DSW1.2
Switching the function of the switching contact
output X2.
DSW1.2 ON: X2 as contactor monitoring
DSW1.2 OFF: X2 as charging status indicator
.
DSW1.3
Enable UDP interface (SmartHome).
Only available for P30 c-series and x-series.
For details, see "UDP Programmer's Guide".
Adjust current - DSW1.6 to DSW1.8
Information
Only one maximum value, which is smaller than or equal to the operating
current according to the type plate, can be set with the DIP switches.
DIP switch
Current rating
Illustration
DSW1.6
DSW1.7
DSW1.8
10 A
DSW1.6
DSW1.7
DSW1.8
13 A
DSW1.6
DSW1.7
DSW1.8
16 A
DSW1.6
DSW1.7
DSW1.8
20 A
DSW1.6
DSW1.7
DSW1.8
25 A
DSW1.6
DSW1.7
DSW1.8
32 A