6.1
General criteria for the site selection
The charging station was constructed for the indoor and outdoor area. Ac-
cordingly, it is necessary to ensure the correct set-up requirements and the
protection of the device at the installation site.
The following criteria must be taken into account when selecting a location:
●
Take into account the local electrical installation regulations, fire preven-
tion measures and accident prevention regulations as well as emer-
gency routes at this site.
●
The charging station may not be installed in potentially explosive atmos-
pheres (EX environment).
●
The charging station may only be installed in stationary applications.
●
Mount the charging station so that it is not located in the direct flow of
passersby and so that no one can trip over connected charging cables
and so that the charging cables do not cover or cross passing pedestrian
and motorized traffic.
●
Do not install the charging station at locations where it is exposed to am-
monia or ammonia gas (e.g. in or at stables).
●
The mounting surface must be sufficiently stable in order to withstand
the mechanical forces.
●
Do not install the charging station at locations where falling objects could
damage the device (e.g. hung up ladders or automobile tires).
●
The device must not be exposed to direct spray water (e.g. neighboring
manual car wash facility, high-pressure cleaner, garden hose).
●
The device should be protected against direct rain as far as possible to
prevent icing, hail damage or similar.
●
If possible, the device should be mounted protected from direct sunlight.
Otherwise, (e.g. set up outside at a parking space) the charging current
specification will be reduced to 16 A if the maximum permitted tempera-
ture is exceeded. The charging process can also subsequently be
switched off.
●
Observe the permissible environmental conditions (see "Technical
data").
Observe the internationally valid installation standards (e.g. IEC 60364-1
and IEC 60364-5-52) and comply with the nationally applicable installation
standards and regulations.