KC-P30
Connections and wiring
Installation manual V3.28
34
© KEBA
Fig. 7-16: Connection to a three-wire IT system with 230 V
7.4
Enable input X1
This function is not available with P30 e-series.
The enable input X1 is equipped for use with a potential-free contact. Using
the enable input, it is possible to control the charging station using external
components (e.g. external key switches, house control, photovoltaic system,
ripple control receivers, ...). The terminal is designed as a spring-type termi-
nal.
Enable contact
State of the charging station
Open
Locked
Closed
Ready for operation
The use of the enable input must be activated with a DIP switch setting
(DSW1.1 to ON), see
.
In addition to the DIP switch setting, starting a charging process using an en-
able input is dependent on the RFID authorization. The table shows under
which conditions charging is enabled.
RFID
DSW 1.1
Description
Off
OFF
Permanent charging enabled − charging is possible at all times.
Off
ON
Charging enabled when X1 is closed.
On
OFF
P30
b-series
and
c-series
(without charging network)
Charging enabled when X1 is closed
OR
RFID authorization is
correct. The state of X1 is no longer checked during the charg-
ing process. The charging process can only be ended early us-
ing an RFID card.
If no RFID cards have been taught in, charging is possible at all
times, both with an open and closed X1.