D3DP 3xx/x
Mounting and installation instructions
Project engineering manual V1.00
28
© KEBA
Illustration 56: Connector mains filter
1
... Control module
2
... Supply module
3
... Axis module
4
... Earth potential
5
... Mains filter
6
... X01A (Line IN) connector
7
... Cable shield with shield clamp
8
... Grounded metallic base plate
Equipotential bounding lines
If the cabinet is not mounted directly on the machine or severals metres
away from the machine, it is recommended to install a equipotential bound
ing line parallel to the cables, which are lead from the cabinet to the ma
chine. The reason for this is, that because of switching processes and indi
rect lightning strikes lowfrequency high compensating currents can be cre
ated, which may be too high for shieldings and especially for the shield con
nectors and can so damage the shield connection.
Содержание D3DP 3 Series
Страница 1: ...D3 DP 3xx x Supply module Project engineering manual V 1 00 Translation of original manual ...
Страница 4: ...D3 DP 3xx x Project engineering manual V1 00 4 KEBA ...
Страница 8: ...D3 DP 3xx x Table of Contents Project engineering manual V1 00 8 KEBA ...
Страница 74: ...D3 DP 3xx x Declaration of conformity Project engineering manual V1 00 74 KEBA 14 Declaration of conformity ...
Страница 75: ...D3 DP 3xx x Declaration of conformity Project engineering manual V1 00 75 KEBA ...
Страница 76: ...D3 DP 3xx x Declaration of conformity Project engineering manual V1 00 76 KEBA ...
Страница 77: ...D3 DP 3xx x Declaration of conformity Project engineering manual V1 00 77 KEBA ...
Страница 80: ...D3 DP 3xx x Glossary Project engineering manual V1 00 80 KEBA Glossary ...
Страница 81: ...D3 DP 3xx x Index Project engineering manual V1 00 81 KEBA Index ...
Страница 82: ...D3 DP 3xx x Index Project engineering manual V1 00 82 KEBA ...