System operation
Thermal consumers:
For this type of consumer, additional parameters are available.
Parameters (example):
Power
18 kW
Priority
01
Type
Thermal consumer
for switch-off
opened
active
yes
Mode
Automatic
Main switch address input
E06
Thermo switch address input
E07
Optimization in the heating up phase
yes
Optimization in the continued heating phase
yes
Maximum on time
0 minutes
Period time-out
0 minutes
Lead time
0 seconds
Follow-up time
0 seconds
Minimum on time / day
0 hours
Minimum on time
0 minutes
Minimum off time
0 minutes
Maximum off time
0 minutes
Application examples:
Optimization in the heating up phase
Optimization in the heating up phase
yes
yes
Initial state:
Main switch address input
Thermo switch address input
Reason for switching the optimization line
opened (=main switch on the
consumer is switched off)
closed (=consumer heats up)
on / release / 0
This means:
Since there is no feedback on the operating state of the consumer,
the consumer is switched on to incorporate it into optimization.