System operation
The thermo switch is not monitored:
Main switch address input
Thermo switch address input
E06
E00
Optimization in the heating up phase
Optimization in the continued
heating phase
yes
yes
Main switch address input
Thermo switch address input
Reason for switching the
optimization line
closed
open (=is not monitored)
on / optimization / 1
That means:
The consumer is in its continued heating phase
immediately
and may be
switched off for optimization purposes.
Chopping operation (no forced chopping! ):
For chopping a consumer, only the times of
Maximum on time
Maximum off time
are configured.
Under some circumstances, waiting until these times have elapsed is not
required, if
for max out, the free power is already sufficient to stop chopping
for max on, optimization needs to be performed earlier
Display for configured chopping operation:
Line state on => The consumer is switched on all the time and the free power is
sufficient, so that no chopping is required.
Line state off => The consumer is chopped, as there is not enough free power
for continuous operation.
Message in the event memory =>
Line switched off, reason optimization
.
The switching interval (in sec.) set in the general parameters is not taken into
account for chopping operation.