System operation
8.7
Alarm parameters
In the
Alarm parameters
area, you can define the type of message for different
alarms.
1.
Select
Main menu > Alarm param. > Enter
.
2.
Start the configuration with
Edit
.
Alarm param.
Programming
Explanation
Type of the
alarm
parameter
Message,
alarm+M, off
Message
only issues a message for a
alarm of this type.
Alarm+M
issues a message
and activates a alarm relay.
Off
does not trigger any action.
You can find a list of all parameters under
"
Alarm parameters menu
"
.
8.8
Password / reset
In the
Password
area, you can define a password and this way lock the device
against unauthorized entries, or reset an existing password. You can also restore
the device default settings here.
1. Select
Main menu > Password > Enter.
The device displays Free, meaning the standard value of 9999 was not changed
and you do not need a password to make entries.
2. Start the configuration with
Edit.
3. Enter a four-digit number as the password.
The device displays
Saved
. As of now, you need to enter a password to make
entries at the device.
If you enter the password, the device stays unlocked for some minutes and is
then locked again automatically.
RESETTING PASSWORD
If a password is no longer necessary, you can unlock the device again.