System operation
Maximum prewarning contact:
The default setting of the contact is closed if active.
Parameters of the prewarning contact:
TYPE
Selection
negative compensation power
higher than available breaking
capacity
Cumulated power higher than
power warning threshold
Trend power higher than power
warning threshold
Off (output deactivated)
Warning threshold
in % of the active
target value
30 to 150 seconds
Hysteresis
in kW
0 to 50000 kW
Minimum on time
in minutes
0 to 999 minutes
Minimum off time
in minutes
0 to 999 minutes
Period time-out
in minutes
0 to 999 minutes
Address prewarning
contact
A48
fixed
prewarning relay
TYPE
Pcum>Plimit
AlarmLimit
30%
on
min.
0.2 min
off
min.
0.2 min
per. idle t.
0.0 min
Addr. prewarn.rel.
A48
¡
í
Edit