System operation
Para. Line
(1, 2, ...)
Programming
Explanation
Feedback
type
Release,
manual_off
manual_on
Defines if the consumer is integrated
into optimization by its feedback (re-
lease), always switched on (manual_on)
or switched off independently of the
trend calculation (manual_off).
Addr.
Pact
Input
E..
Address of the message input used to
determine the actual power consump-
tion of the consumer using an energy
measuring module.
-- in development --
switch-off
in case of
malfunc-
tion
on / off
Defines if the consumer is switched off
in case of a malfunction.
The following malfunctions can trigger an emergency switch-off:
the cumulated measuring period power is higher than the target value
the limit value "maximum actual power" is exceeded
Counter pulse failure counter 1
Counter pulse failure counter 2
Counter pulse failure counter 3
Counter pulse failure counter 4
Counter pulse failure counter 5
4.
Configure the time-dependent parameters
of the consumer with
Time
and
Edit.
Times line
(1, 2,...)
Programming
Explanation
Per.
Time-out
Numerical value in
min
Defines the time the consumer
definitely stays switched on from the
beginning of the period
Lead time
Numerical value in
sec
Defines the time which the consumer
is switched on earlier, since it only
achieves its power after this time has
elapsed.