System operation
Main switch is switched on:
Main switch address input
Thermo switch address input
Reason for switching the
optimization line
closed
closed (=consumer heats up)
on / optimization / 1
That means:
The consumer is switched on, feedback on the operating state of the con-
sumer is available and the consumer may be switched off for optimization
purposes.
Thermo switch opens:
Main switch address input
Thermo switch address input
Reason for switching the
optimization line
closed
opened (=consumer has
reached its temperature)
on / optimization / 1
That means:
The consumer is in the continued heating phase (after the first opening of
the thermo switch) and may be switched off for optimization purposes.
No optimization in the heating up phase:
Main switch address input
Thermo switch address input
E06
E07
Optimization in the heating up phase
Optimization in the continued
heating phase
no
yes
Main switch address input
Thermo switch address input
Reason for switching the
optimization line
closed
closed
on / heating / 1
That means:
The consumer is in its heating up phase but cannot be switched off
for optimization purposes.