V2.01
25359_EDEBD
A0279-2320-1_EN
44
Technical Data
12 Technical Data
12.1 Measuring and display values
Voltage
RMS value of a
measuring interval
Phase - 0 or phase - phase, depending on
configuration
Units
V, kV;] display switches automatically
Display range
0.00 kV to 99.9 kV
Measuring range
30 - 690 VAC (max. permissible value: 790
VAC)
Current
(apparent current)
RMS value of a
measuring interval
Actual value per phase
Units
[A; kA] display is switched automatically
Display range
0.00 A to 999 kA
Measuring range
0.015 - 5 A (max. permissible value: 6 A)
Frequency
Network frequency
measurement
f
Network
Units
[Hz]
Measuring range
41 - 70 Hz
Apparent power
Calculation
S
tot
, 3-phase
Units
kVA
Display range
0.0 VA to 9999.9 kVA
Active power
Calculation
P
total
; 3-phase
Units
kW
Display range
0.0 W to 9999.9 kW
Reactive power
Calculation —> ind.
and cap.
Q
total
; Q
miss
; distinction between ind./cap.
Units
kvar
Display range
0.0 var to 9999.9 kvar
Power factor
Calculation —> ind.
and cap.
CosPhi; distinction between ind./cap.
CosPhi in display
Display range
CosPhi 0.10 ind. <—1 —>0.10 cap.
Temperature
Measuring range
-10°C to +60°C
Harmonics
Distortion factor
(THD) for voltage
Voltage: THD-U
Partial distortion
factors
3
rd
; 5
th
; 7
th
; 9
th
; 11
th
; 13
th
;
voltage harmonic
Units
[%]
Measuring range
0.00% to 100%
Содержание multicomp F144-MS-1V1C1TI6RO-3
Страница 65: ...Notes 25359_EDEBDA0279 2320 1_EN 65...
Страница 66: ...Notes 25359_EDEBDA0279 2320 1_EN 66...
Страница 67: ...Notes 25359_EDEBDA0279 2320 1_EN 67...