Description of the display window
Switching interval (default setting 8 seconds, setting range 0 to 10 seconds):
This value defines the time the controller is idle between two switching operations.
Alarm cos phi (default setting ind. 0.92, setting range ind. 0.70 to 1.0):
This value is connected to the message Facility too small. If this value is not reached
after the alarm delay has elapsed, despite all stages being switched on, the message
PFC too small is displayed.
Attenuation Qmiss (default settings 2, setting range 0 to 9):
This value defines the attenuation of the display and control behavior to prevent rapid
parameter changes if there is no compensation power.
Attenuation U (default setting 0, setting range 0 to 9):
This value defines the display attenuation to prevent rapid parameter changes of the
measuring voltage.
Attenuation I (default setting 2, setting range 0 to 9):
This value defines the display attenuation to prevent rapid parameter changes of the
measuring current.