Technical Data
12.7 Hardware inputs and outputs
12.7.1 Hardware inputs
Voltage
measuring
input
U
PH-N
or U
PH-PH
30 - 690 VAC (max. permissible value: 790
VAC)
Input impedance
1500 kOhm
Measuring range
1 measuring range,
measuring voltage transformer can be
programmed
Current
measuring
input
I
L1
or IL2 or I
L3
0.015 - 5 A (max. permissible value: 6 A)
Power consumption
0.3 VA at 6 A, 0.05 VA at 1.2 A
Measuring range
1 measuring range,
current transformer can be programmed
Analog input
PT 1000 measurement
sensor
Temperature measurement -10 °C to 60 °C,
+/- 2 °C
max. cable length < 3 meters
12.7.2 Hardware outputs
Alarm relay
Switching capacity
250 V (AC) / 2 A floating
Capacitor stage
relay
Switching capacity
250 V (AC) / 2 A floating
Serial interface BUS
RS485 for connection to the Modbus
Protocol, baud rate
Modbus RTU,
bud rate 4800, 9600, 19200, 38400
Parity none, even, odd
Address assignment
Modbus:
manual setting on the device, address 1 to
247